www.beckhoff.com/zh-sg/

EP2316-0008 | EtherCAT Box, 8-channel digital input + 8-channel digital output, 24 V DC, 10 µs, 0.5 A, D-sub

Image similar, may contain optional accessories
EP2316-0008 | EtherCAT Box, 8-channel digital input + 8-channel digital output, 24 V DC, 10 µs, 0.5 A, D-sub

EP2316-0008 | EtherCAT Box, 8-channel digital input + 8-channel digital output, 24 V DC, 10 µs, 0.5 A, D-sub

EtherCAT signal input
EtherCAT signal output
D-sub, 25-pin
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
Signal status display
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1-8 | Input
9-16 | Output
17-22 | +24 V DC US
23-25 | GND
1 | +24 V DC US
2 | +24 V DC UP
3 | GND
4 | GND
Top view 
I/O connection 
Connector assignment 
EP2316-0008 | EtherCAT Box, 8-channel digital input + 8-channel digital output, 24 V DC, 10 µs, 0.5 A, D-sub

EP2316-0008 | EtherCAT Box, 8-channel digital input + 8-channel digital output, 24 V DC, 10 µs, 0.5 A, D-sub

The EP2316-0008 EtherCAT Box combines eight digital inputs (upper socket connector) and eight digital outputs (lower socket connector) in a single device. The inputs have a filter of 10 µs. The outputs process load currents up to 0.5 A and are short-circuit-proof and protected against reverse polarity. The signal status is displayed via the optional plug connector. The signal connection is made via spring-cage connectors, optionally available in 1- and 3-pole versions. The module is delivered without connectors.

 

The supply of the connected sensors is done by an internal, short-circuit proof driver module with a total of 0.5 A for all sensors. The outputs are supplied via flush mounted. All outputs are short-circuit-proof and protected against reverse polarity. The 16-channel design offers a very high channel density in a very small space.

Product status:

regular delivery

Product information

Technical dataEP2316-0008
ProtocolEtherCAT
Bus interface2 x M8 socket, 4-pin, a-coded, shielded
SpecificationEN 61131-2, type 1/3
Number of channels8 inputs + 8 outputs
Input/output connectionsD-sub socket, 25-pin, UNC4-40
Input filter10 µs
“0” signal voltage-3…+5 V
“1” signal voltage11…30 V, 6 mA input current (EN 61131-2, type 3)
Sensor supplyfrom control voltage, max. 0.5 A, short-circuit proof in total
Load typeohmic, inductive, lamp load
Rated load voltage24 V DC (-15%/+20%)
Max. output current0.5 A per channel, individually short-circuit proof
Switching timestyp. TON: 60 µs, typ. TOFF: 300 µs
Short-circuit currenttyp. 1.5 A
Distributed clocksyes
Auxiliary power currenttyp. 20 mA + load
Current consumption from US120 mA
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation500 V
Special featuresideal for high number of channels
Weightapprox. 165 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing data8 x M8, 4 x M12
Dimensions (W x H x D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3