KL2798 | Bus Terminal, 8-channel solid state relay output, 30 V AC, 48 V DC, 2 A, potential-free

Image similar, may contain optional accessories
KL2798 | Bus Terminal, 8-channel solid state relay output, 30 V AC, 48 V DC, 2 A, potential-free

KL2798 | Bus Terminal, 8-channel solid state relay output, 30 V AC, 48 V DC, 2 A, potential-free

Signal
1…8
Power contact
+24 V DC
Power contact
0 V
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 1'
Output 2'
Output 3'
Output 4'
Output 5'
Output 6'
Output 7'
Output 8'
KL2798 | Bus Terminal, 8-channel solid state relay output, 30 V AC, 48 V DC, 2 A, potential-free

KL2798 | Bus Terminal, 8-channel solid state relay output, 30 V AC, 48 V DC, 2 A, potential-free

The digital KL2798 Bus Terminal provides eight switches that can be used like a relay contact for AC/DC voltages. The electronic switch is realized through high-performance MOSFET transistors with low switch-on resistance. The switch itself is not short-circuit proof, but due to its high pulse current capability it can cope with current until an external fuse triggers a switch-off.

Wear resistance increases the availability of the application. Resistive and inductive loads can be switched up to a rated voltage of 30 V AC/DC, completely resistive loads also up to a rated voltage of 48 V DC.

High peak voltages and electromagnetic interference pulses are prevented.

Product status:

regular delivery

Product information

Technical dataKL2798
Connection technology2-wire
Number of outputs8 x make contacts
Max. output current2 A per channel, ∑ 10 A
Breakdown voltage80 V
Peak current5 A (100 ms), < 50 A (10 ms)
Short-circuit currentnot short-circuit proof, see peak current
Reverse polarity protection–
Isolation voltage (channel/channel)< 200 V
Electrical isolation500 V (K-bus/field potential)
Switching on speedtyp. 1.8 ms, max. 5 ms
Switching off speedtyp. 30 ms, max. 50 ms
On-resistancetyp. 0.03 Ω
Current consumption power contacts–
Current consumption K-bus80 mA
Bit width in the process image8 outputs
Special featuressubstitute for relay contacts, potential-free
Operating temperature0…55°C
Storage temperature-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL
Housing dataHD housing
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Marking–
Wiringsolid conductors (s): direct plug-in technology; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Stripping length8…9 mm
Dimensions (W x H x D)12 mm x 100 mm x 68 mm

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Material complianceKL2798
REACH SVHCno
POPcompliant
RoHScompliant with exemption
RoHS exemption7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors
China-RoHSwww.beckhoff.com/china-rohs-io
CA Prop65www.beckhoff.com/prop65
DisclaimerThis statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply.