The AS-Interface master terminal is an extended master according to profile M3 and enables the direct connection of AS-Interface slaves. The AS-Interface-compliant interface supports digital and analog slaves, versions 2.0 and 2.1, safety slaves and slaves with Combined Transaction Type 1 (profile S-7.3 and 7.4). Process data exchange, parameterization and the diagnosis are fieldbus-independent. Together with the different Bus Couplers, the KL6211 represents a universal AS-Interface/fieldbus gateway. Together with the BK3120, the PROFIBUS DP V1 services can be used for communication with the KL6211. Unlike the KL6201 AS-Interface master terminal, the KL6211 features power contacts. This enables direct connection to the AS-Interface supply via the KL9520 AS-Interface potential feed terminal or the KL9528 power supply terminal.
Product status:
KL6211: regular delivery
KS6211: on request | Please contact sales.
Product information
| Technical data | KL6211 |
|---|---|
| Technology | AS-Interface |
| Number of channels | 1 |
| Number of slaves | 31 for V 2.0, 62 for V 2.1 |
| Specification version | AS-Interface V 2.0, V 2.1 |
| Slave types | digital and analog |
| Diagnostics | power failure, slave failure, parameterization fault |
| AS-Interface address
assignment | via configuration or automatic |
| Cycle time | max. 5 ms (31 devices) |
| Connection | 2 lines via spring-loaded technology |
| Current consumption K-bus | typ. 55 mA (K-bus), typ. 60 mA (AS-Interface) |
| Current consumption power contacts | typ. 60 mA + load |
| Electrical isolation | 500 V (AS-Interface/K-bus) |
| Power contacts | yes |
| Bit width in the process image | selectable: 12 bytes, 22 bytes or 38 bytes, of which 6 bytes parameter interface |
| Configuration | via fieldbus parameter interface, DP-V1 or Bus Coupler through KS2000 |
| Weight | approx. 55 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring level | for all KSxxxx Bus Terminals |
| Approvals/markings | CE, UL |
| Housing data | KL-12-8pin | KS-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| KL6211 | Bus Terminal, 1-channel communication interface, ASi, master |
| KS6211 | Bus Terminal, 1-channel communication interface, ASi, master, pluggable wiring level |
| KL6211-0011 | Bus Terminal, 1-channel communication interface, ASi, master, preset to 38 bytes K-bus interface, supports up to 62 AS-Interface slaves (4 K-bus cycles) |
Loading content ...
| Material compliance | KL6211 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |