Sídlo Česká republika
Beckhoff Automation s.r.o.

Sochorova 23
61600 Brno, Česká republika

+420 511 189 250
info.cz@beckhoff.com
www.beckhoff.com/cs-cz/

EP3754-0702 | EtherCAT Box, 4-channel analog input, ID switch, multi-function, M12New

Image similar, may contain optional accessories
EP3754-0702 | EtherCAT Box, 4-channel analog input, ID switch, multi-function, M12

EP3754-0702 | EtherCAT Box, 4-channel analog input, ID switch, multi-function, M12

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | +Uv
2 | Input +
3 | -Uv
4 | Input -
5 | Shield
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
EP3754-0702 | EtherCAT Box, 4-channel analog input, ID switch, multi-function, M12

EP3754-0702 | EtherCAT Box, 4-channel analog input, ID switch, multi-function, M12

The EP3754-0702 EtherCAT Box has four analog multi-functional inputs, which can be parameterized individually and extensively:

 

  • voltage measurement: -10…+10 V, 0...10 V
  • current measurement: ±20 mA, 4...20 mA, 0...20 mA
  • resistance measurement: 20 Ω…4 kΩ in 2-/3-/4-wire connection
  •  RTD measurement in 2-/3-/4-wire connection
  • thermocouple measurement

 

The measured values are digitized with a 16-bit resolution and transmitted electrically isolated to the higher-level automation device. The input filters and their associated conversion times are configurable in a wide range. The inputs can, if required, be scaled differently, and automatic limit value monitoring is also available. EtherCAT is used for parameterization purposes. The EtherCAT Box can be used universally for a wide range of measurement tasks thanks to the flexible parameter settings.

The EP3754-0702 has three additional hexadecimal ID switches. In this way, an individual address from 0...4095 can be set, allowing unique identification regardless of installation position, as required by some device profiles for certain industries, such as the semiconductor industry.

Product status:

product announcement | estimated market release 4th quarter 2025

Product information

Technical dataGeneral
ProtocolEtherCAT
Bus interface2 x M8 socket, 4-pin, a-coded, shielded
Number of configurable IDs4096
Number of inputs4
Input connectionsM12 x 1, 5-pin, A-coded
Nominal voltage24 V DC (-15%/+20%)
Distributed clocksno
Current consumption from US~ 120 mA
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation500 V
Weightapprox. 200 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Technical dataAnalog input | Current
Conversion time~ 100 µs
Resolution16 bit (incl. sign)
Signal range | Nominal -20 mA/0/+4…+20 mA
Common mode voltage UCMmax. 12 V
Internal resistancetyp. 85 Ω
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable (free numeric filters)
Ground referencedifferential
Sensor supplyfrom control voltage, max. 180 mA per channel, short-circuit proof
Technical dataAnalog input | Voltage
Conversion time~ 100 µs
Resolution16 bit (incl. sign)
Signal type-10/0…+10 V
Common mode voltage UCMmax. 12 V
Internal resistance> 200 kΩ
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable (free numeric filters)
Ground referencedifferential
Sensor supplyfrom control voltage, max. 180 mA per channel, short-circuit proof
Technical dataAnalog input | Thermocouple
Conversion time~ 5 ms
Resolution16 bit (incl. sign)
Sensor typestype B, C, E, J, K, L, N, R, S, T, U, mV measurement
Signal type°C (thermocouple)
Common mode voltage UCMmax. 12 V
Internal resistance~ 1 MΩ
Measuring rangedepending on sensor type; preset value is type K, -100…+1370°C
Measurement error/uncertainty< ±0.3% for type K (relative to full scale value; further types see documentation)
Input filterconfigurable
Special featurescompensation for the cold junction
Technical dataAnalog input | Resistance thermometer (RTD)
Connection method2-, 3-, 4-wire
Conversion time~ 5 ms
Resolution16 bit (incl. sign)
Sensor typesPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000
Signal type°C (RTD)
Measuring range-200…+850 °C (Pt sensors); Pt100 default setting
Measurement error/uncertainty< ±0.5°C (Pt sensors in 4-wire connection)
Input filterconfigurable
Technical dataAnalog input | Resistance
Connection method2-, 3-, 4-wire
Conversion time~ 5 ms
Resolution16 bit (incl. sign)
Sensor typesresistance (20 Ω…4 kΩ)
Signal typeΩ
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable
Housing data8 x M8, 4 x M12, ID switch
Dimensions (W x H x D)30 mm x 155 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3