DetachFixClose

Headquarters United Arab Emirates
Beckhoff Automation FZE

C# 608, Dubai Silicon Oasis
P.O. Box No. 341007
Dubai, United Arab Emirates

+971 4 5015480
info@beckhoff.ae
www.beckhoff.com/ar-ae/

EL2904 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, TwinSAFE

EL2904 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, TwinSAFE

EL2904 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, TwinSAFE

Output 1, 2
Output 3, 4
Diagnostic 1, 2
Diagnostic 3, 4
Power contact
+24 V
Power contact 0 V
Output 1, 2
Output 3, 4
Top view 
Contact assembly 
EL2904 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, TwinSAFE

EL2904 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, TwinSAFE

The EL2904 TwinSAFE component is a digital output terminal with four channels. It switches 24 V DC actuators with up to 0.5 A per channel and has four fail-safe outputs. The outputs are controlled by a TwinSAFE Logic-capable component via FSoE. The component automatically switches off if it detects an error (fail-stop).

The EL2904 has safety parameters to specifically adapt the functionality to the respective safety requirements. For example, a current measurement at the outputs and a test of the outputs can be configured in order to be able to detect cross-circuits among other things and to react appropriately.

In addition, standard outputs can be activated for the EL2904. As a result, corresponding standard outputs are available in the process image in parallel and internally ANDed with the safe outputs of the EL2904. The safe output signals, which are controlled by a TwinSAFE Logic, thus issue the safe release for the standard signals, which can be triggered by the non-safety oriented control system independently of the cycle of the safety controller and FSoE. This allows faster switching times of the outputs, provided that the safety controller issues the necessary release for the output.

The safety parameters are not stored directly on the component, but are transmitted to the component via a TwinSAFE Logic-capable component when the safety application is started. This simplifies service procedures, because the component can simply be replaced. The safety-relevant parameters are transferred to the new component when the safety application is restarted.

 

Special features:

  • 4 safe outputs
  • integrated current measurement
  • testing of the channels can be activated
  • Standard outputs can be activated with integrated AND connection with a safe output signal

Product status:

regular delivery

Product information

Technical dataEL2904
Connection technology1-/2-wire
Specificationoutput of output signals
Number of outputs4
Max. output current0.5 A (per channel), min. 20 mA (with active current measurement)
ProtocolTwinSAFE/Safety over EtherCAT
Fault response time≤ watchdog time (parameterizable)
Current consumption power contactsload-dependent
Current consumption E-bustyp. 221 mA
Installation positionhorizontal
Safety standardDIN EN ISO 13849-1:2008 (Cat. 4, PL e) and EN 61508:2010 (SIL 3)
Weightapprox. 100 g
IP protection ratingIP20
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataEL-24-2x8pin
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)24 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG28…14,
st*: AWG28…14,
f*: AWG26…16
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Loading content ...

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use