DetachFixClose

KL3454 | 4-channel analog input terminal 4…20 mA

KL3454 | 4-channel analog input terminal 4…20 mA

KL3454 | 4-channel analog input terminal 4…20 mA

Run LED 1
Error LED 1
Run LED 3
Error LED 3
Run LED 2
Error LED 2
Run LED 4
Error LED 4
Power contact
+24 V
Power contact 0 V
Input 1
+24 V
Input 3
+24 V
Input 2
+24 V
Input 4
+24 V
Top view 
Contact assembly 
KL3454 | 4-channel analog input terminal 4…20 mA

KL3454 | 4-channel analog input terminal 4…20 mA

The KL3454 analog input terminal processes signals in the range between 4 and 20 mA. The current is digitised to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device. In the KL3454, the four inputs are 2-wire versions and have a common ground potential. The 24 V power contact is connected to the terminal, in order to enable the connection of 2-wire sensors without external supply. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. Overload is detected. The terminal status is relayed to the controller via the K-bus. The run LEDs indicate the data exchange with the Bus Coupler, the error LEDs overload or wire breakage.