The ELM300x EtherCAT Terminals are designed for flexible voltage measurement from 20 mV to 30 V in eleven measuring ranges. The measuring range is selected in the CoE, as are the other setting options such as the filter parameters. Irrespective of the signal configuration, all ELM modules have the same technological properties. The ELM300x modules for voltage measurement offer a maximum sampling rate of 10,000 or 20,000 samples per second. The 2-pin plug (push-in) can be removed for maintenance purposes without releasing the individual wires.
For the ELM300x-0030, an individual calibration certificate is available, currently as a choice of DAkkS or IS0 17025-compliant certificate. The certificate is issued by an accredited service provider in collaboration with Beckhoff. The desired calibration certificate can be downloaded from here using the respective serial number.
Extensive documentation is available from Beckhoff sales, support or measurement@beckhoff.com.
Product status:
regular delivery
Product information
System data | ELM300x |
---|---|
Voltage measurement | ±30/10/5/2.5/1.25 V, ±640/320/160/80/40/20 mV, 0…5/10 V |
Technical data | ELM3004-0030 |
---|---|
Number of channels | 4 |
Technology | voltage measurement |
Signal type | differential |
Connection technology | 2-wire |
Connection type | push-in, service plug 2-pin |
Max. sampling rate | max. 100 µs/10 ksps (per channel, simultaneously) |
Oversampling factor | n = 1…100 selectable (max. 10 ksamples/s) |
Internal resistance | > 500 kΩ (30 V); > 4 MΩ (others) |
Measurement error/ uncertainty | typ. < ±50 ppm/±0.005 % in some measuring ranges, relative to the respective full scale value, see documentation |
Temperature coefficient | typ. < 1 ppm/K |
Functional diagnostics | yes |
Connection diagnostics | broken wire/short circuit |
Distributed clocks | yes, accuracy << 1 µs |
Resolution | 24 bit (incl. sign) |
Electrical isolation channel/channel | no |
Electrical isolation channel/bus | 707 V DC (type test) |
Electrical isolation channel/SGND | 707 V DC (type test) |
Current consumption power contacts | – |
Current consumption E-bus | typ. 470 mA |
Weight | approx. 350 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Thermal dissipation | typ. 3 W |
Special features | ExtendedRange 107 %, free numeric filter, TrueRMS, integrator/differentiator, non-linear scaling, PeakHold, calibrated version of ELM3004-0000 |
Approvals/markings | CE, UL |
Housing data | ELM-30-xpin |
---|---|
Design form | metal housing with signal LEDs |
Material | zinc die-cast |
Dimensions (W x H x D) | 30 mm x 100 mm x 95 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.2…1.5 mm², st*: 0.2…1.5 mm², f*: 0.25…0.75 mm² |
Connection cross-section AWG | s*: AWG 24…14, st*: AWG 24…14, f*: AWG 24…14 |
Stripping length | 8…9 mm |
*s: solid wire; st: stranded wire; f: with ferrule
Technical data | |
---|---|
ELM3004-0030/000079852 | ELM3004-0030 with external calibration certificate type ISO 17025, external service providers |
ELM3004-0030/000079853 | ELM3004-0030 with external calibration certificate type DAkkS, external service providers |