OdpniPripniZapri

EP2809-0042 | EtherCAT Box, 16-channel digital output, 24 V DC, 0.5 A, M12

EP2809-0042 | EtherCAT Box, 16-channel digital output, 24 V DC, 0.5 A, M12

EP2809-0042 | EtherCAT Box, 16-channel digital output, 24 V DC, 0.5 A, M12

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power IN
Power OUT
1 | Tx+
2 | Rx+
3 | Tx-
4 | Rx-
1 | +24 V DC UP
2 | Output B
3 | GNDP
4 | Output A
5 | n.c.
1 | GNDP
2 | GNDS
3 | FE
4 | +24 V DC US
5 | +24 V DC UP
2-wire
3-wire
Top view 
I/O connection 
Connector assignment 
EP2809-0042 | EtherCAT Box, 16-channel digital output, 24 V DC, 0.5 A, M12

EP2809-0042 | EtherCAT Box, 16-channel digital output, 24 V DC, 0.5 A, M12

The EP2809-0042 EtherCAT Box is intended for processing digital/binary signals. It switches the binary control signals from the automation device to the actuators at the process level. The outputs process an output current of up to max. 0.5 A. A short-term overload is possible. The outputs are short-circuit proof. The total current of all outputs is limited to 16 A. 7/8" connectors are used for the input/output of the supply voltage.

 

The signal status of the channels is indicated by LEDs. The signals are connected via M12 screw type connectors. Two channels are available per M12 socket. The 16-channel design offers a very high channel density in a very small space.

 

The EtherCAT connection is made via d-coded M12 sockets.

Product status:

regular delivery

Product information

Technical dataEP2809-0042
ProtocolEtherCAT
Bus interface2 x M12 socket, 4-pin, D-coded
Number of outputs16
Ohmic switching current
Output connectionsM12 x 1, 5-pin, a-coded
Minimum permitted load
Load typeohmic, inductive, lamp load
Nominal output voltage24 V DC (-15%/+20%)
Max. output current0.5 A per channel, individually short-circuit proof, ∑ 16 A
Switching timestyp. TON: 60 µs, typ. TOFF: 300 µs
Short-circuit currenttyp. 1.9 A
Distributed clocks
Current consumption from UStyp. 130 mA
Auxiliary power currenttyp. 20 mA + load
Power supply connectionfeed: 1 x 7/8" plug, 5-pin; downstream connection: 1 x 7/8" socket, 5-pin
Operating cycles mech. (min.)
Operating cycles electr. (min.)
Electrical isolation500 V
Weightapprox. 440 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, (UL in preparation)
Housing data7/8" infeed
Dimensions (W x H x D)60 mm x 150 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4