The EL2872 digital output terminal offers a very compact design with its 16 channels. A 20-pin contact strip enables the secure connection of plug connectors using insulation displacement contact, as is usual for ribbon cables and special round cables. This significantly simplifies the wiring of many channels. The signal states of the channels are indicated by LEDs.
Special features:
- connection of different load types possible (resistive, inductive, lamp load)
- ideal for valve terminals with multi-pin plug connection
- max. output current 0.5 A per channel
- short-circuit-proof outputs and reverse polarity protection
- direct connection of connectors with insulation displacement contacts
Product status:
regular delivery
Product information
| Technical data | EL2872 |
|---|---|
| Connection technology | flat-ribbon cable |
| Number of outputs | 16 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Current carrying capacity | max. 1 A per connection pin |
| Load type | resistive, inductive, lamp load |
| Distributed clocks | – |
| Max. output current | 0.5 A (short-circuit proof) per channel |
| Short-circuit current | typ. < 2 A |
| Reverse polarity protection | yes |
| Switching-off energy | < 150 mJ/channel |
| Switching times | typ. TON: 60 µs, typ. TOFF: 300 µs |
| Current consumption E-bus | typ. 130 mA |
| Current consumption power contacts | typ. 25 mA + load (no power contacts) |
| Bit width in the process image | 16 outputs |
| Configuration | no address or configuration setting |
| Electrical isolation | 500 V (E-bus/field potential) |
| Special features | ideal for multi-pin connector valve terminals |
| Weight | approx. 55 g |
| Operating temperature | -25…+55°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Housing data | EL-12-FRC |
|---|---|
| Design form | compact terminal housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | flat-ribbon cable connection |
| Connection cross-section | common flat-ribbon cables, AWG28, spacing 1.27 mm |
| Connection cross-section AWG | AWG28 |
| Stripping length | – |
| Dimensions (W x H x D) | 12 mm x 100 mm x 73 mm |
*s: solid wire; st: stranded wire; f: with ferrule
Loading content ...
| Material compliance | EL2872 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |