The KL8548 is an 8-channel analog output module for 0 to 10 V. The analog values must be specified individually for each channel via the controller or via a potentiometer. The actual output value is indicated by a bar graph. The position of the potentiometer is readable by the controller in each mode of operation.
Product status:
regular delivery
Product information
| Technical data | KL8548 |
|---|---|
| Number of inputs | 8 (potentiometer) |
| Number of outputs | 8 (0…10 V) |
| Signal voltage | 0…10 V |
| Resolution | 12 bit |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Current consumption K-bus | 50 mA in ECO mode, 95 mA in full scale mode |
| Power supply | 24 V connection |
| Bus interface | K-bus connection IN/OUT |
| I/O connection | flat-ribbon cable connection, 20-pin, shielded |
| Switch settings | auto/manual, potentiometer |
| Diagnostics LED | yellow |
| Special features | Potentiometers and switches can be read via the PLC. Analog values are displayed in the form of bar charts. |
| Weight | approx. 215 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
Loading content ...
| Material compliance | KL8548 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |
Loading content ...
© Beckhoff Automation 2026 - Terms of Use