PROFINET is the open Industrial Ethernet standard of the PNO (PROFIBUS Nutzerorganisation). Internationally established IT standards are used for communication. PROFINET RT describes the data exchange between controllers and field devices and can be used in standard Ethernet networks. Commercial switches are used for networking purposes. Linking to any PROFINET controller takes place via the GSDML basic device file.
The BK9053 Bus Coupler connects PROFINET with the modular, extendable electronic terminal blocks. One unit consists of one Bus Coupler, any number from 1 to 64 terminals (255 with K-bus extension) and one end terminal.
The Bus Couplers recognize the terminals to which they are connected, and perform the assignment of the inputs and outputs to the words of the process image automatically.
Product status:
Regular delivery
Product information
- Technical data
- Accessories
- Documentation and downloads
- Beckhoff Information System
- Additional products
- Related products
System data | PROFINET | BK9053 |
---|---|
Number of I/O stations | only limited by IP addresses |
Number of I/O points | depending on controller |
Data transfer medium | 4 x 2 twisted pair copper cable; category 3 (10 Mbit/s), category 5 (100 Mbit/s) |
Distance between stations | 100 m between hub/switch and Bus Coupler or between Bus Coupler and Bus Coupler |
Data transfer rates | 100 Mbit/s |
Topology | star wiring |
Technical data | BK9053 |
---|---|
Number of Bus Terminals | 64 (255 with K-bus extension) |
Max. number of bytes fieldbus | 512 byte input and 512 byte output |
Digital peripheral signals | 512 inputs/outputs |
Analog peripheral signals | 256 inputs/outputs |
Protocol | PROFINET RT (Class B) |
Configuration possibility | via KS2000 |
Data transfer rates | 10/100 Mbit/s, automatic recognition of the transmission rate |
Bus interface | 1 x RJ45 |
Power supply | 24 V DC (-15 %/+20 %) |
Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
Starting current | 2.5 x continuous current |
Recommended fuse | ≤ 10 A |
Current supply K-bus | 1750 mA |
Power contacts | max. 24 V DC/max. 10 A |
Electrical isolation | 500 V (power contact/supply voltage/fieldbus) |
Weight | approx. 100 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Housing data | BKxx50, BCxx50 |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 44 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule