The EL3314-0030 analog input terminal allows four thermocouples to be connected directly. The circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearization across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through internal high-precision temperature measurement at the terminal. The EL3314-0030 can also be used for mV measurements.
For the EL3314-0030, an individual calibration certificate is available, currently as a choice of DAkkS or IS0 17025-compliant certificate. The certificate is issued by an accredited service provider in collaboration with Beckhoff.
The desired calibration certificate can be downloaded from here using the respective serial number.
Product status:
regular delivery
Product information
- Technical data
- Accessories
- Documentation and downloads
- Beckhoff Information System
- Further information
- Related products
Technical data | EL3314-0030 |
---|---|
Number of inputs | 4 |
Technology | Temperature measurement (TC) |
Connection method | 2-wire |
Signal type | differential |
Temperature measurement (thermocouple) | type B, C, E, J, K, L, N, R, S, T, U (default setting: type K) |
Measurement uncertainty (temperature measurement) | at 23 °C ambient temperature, with internal cold junction, according type: B: ±2.6 °C; C: ±2.2 °C; E: ±1.6 °C; J: ±1.6 °C; K: ±1.6 °C; L: ±1.5 °C; N: ±1.6 °C; R: ±2.2 °C; S: ±2.3 °C; T: ±1.6 °C; U: ±1.5 °C; for further details see documentation |
Voltage measurement | ±78 mV |
Measurement uncertainty (voltage measurement) | at ±78 mV, 23 °C ambient temperature: < ±0.06 % (relative to full scale value) |
Resolution | 24 bit, presentation adjustable: 0.1/0.01/0.001 °C per digit or 10 nV per digit |
Input filter limit frequency | typ. 1 kHz |
Conversion time | approx. 1.6 s up to 5 ms, depending on configuration and filter setting, default: approx. 110 ms |
Distributed clocks | – |
Power supply | via the E-bus |
Current consumption E-bus | typ. 200 mA |
Current consumption power contacts | – |
Electrical isolation | 500 V (E-bus/signal voltage) |
Special features | channel by channel wire break detection, internal and external cold junction, firmware filter adjustable |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable (see documentation) |
Calibration certificate (analog) | externally calibrated |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG 28…14, st*: AWG 28…14, f*: AWG 26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule