IP5209-B318 | Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 1 Vpp, M23, integrated T-connector (service phase)

IP5209-B318 | Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 1 Vpp, M23, integrated T-connector (service phase)

IP5209-B318 | Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 1 Vpp, M23, integrated T-connector (service phase)

Fieldbus connection (design depends
on the fieldbus)
M23 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
Encoder connection
1 | B
2 | +5 V DC sensor
3 | R
4 | R
5 | A
6 | A
7 | n.c.
8 | B
9 | n.c.
10 | GNDS
11 | GNDS
12 | +5 V DC sensor
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
IP5209-B318 | Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 1 Vpp, M23, integrated T-connector (service phase)

IP5209-B318 | Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 1 Vpp, M23, integrated T-connector (service phase)

The SinCos module IP5209-Bxxx serves as interface for the direct connection of a measuring sensor, for example a measuring probe with sinusoidal voltage output 1 VPP to the higher-level fieldbus. In contrast to the standard version, instead of a voltage input the special IP5209-Bxxx-1000 version has a current input for 11 µAPP measuring probes. The measuring signal is processed, interpolated and made available as a 32 bit value. The signal period resolution is 10 bits, i.e. 1024 steps. The reference mark is also stored in a 32 bit value. The current count and the reference mark value can be read. The cut-off frequency for the measuring signal inputs is 100 kHz.

Product status:

regular delivery

Product information

Technical data position measurementIP5209-Bxxx
Connection technologyM23 connector with outer thread, 12-pin
Number of channels1
Nominal voltage24 V DC (-15%/+20%)
Signal input1 VPP
Encoder supply5 V DC
Sensor supply5 V DC from control voltage, max. 0.5 A
Cut-off frequency100 kHz (scanning of the input signals with 500 kHz)
Resolution10 bit, 1024 steps per period
Commandsset count, evaluate reference mark latch, change of direction, frequency control
Transmission rate
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Current consumption from US (without sensor current)130 mA
Bit width in the process imageinput/output: 2 x 32 bit data, 1 x 8 bit control/status
Electrical isolationdepends on the bus system
Technical dataIP5209-B318
Configurationvia KS2000 or the controller, DP-V1 extensions are supported
Transmission rateautomatic detection up to 12 Mbaud
Bus interface1 x M12 socket, 5-pin, 1 x M12 plug, 5-pin (tee-connector integrated), B-coded
Transmission mediumshielded copper cable, 2 x 0.25 mm²
Power supplycontrol voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Box supply current85 mA + current consumption of sensors, max. 0.5 A
Auxiliary power currentaccording to I/O type
Electrical isolationcontrol voltage/fieldbus: no, control voltage/inputs or outputs: according to I/O type
Data transfer timeapprox. 0.5 ms with 10 stations each with 32 bit input and output
Operating temperature0…55°C
Storage temperature-25…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing dataXXL housing
Dimensions (W x H x D)30 mm x 210 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3
Ordering information
IP5209-B318Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 1 Vpp, M23, integrated T-connector (service phase)
IP5209-B318-1000Fieldbus Box, 1-channel encoder interface, PROFIBUS, SinCos, 11 µApp, M23, integrated T-connector (service phase)
Material complianceIP5209-B318
CAS No.7439-92-1, 556-67-2, 115-86-6
REACH SVHCLead, Octamethylcyclotetrasiloxane, Triphenyl phosphate
REACH Annex XVIIcompliant
REACH Annex XIVcompliant
SCIP No.2891ebe2-fbf0-4948-b1db-f7a3a34cb218
POPcompliant
RoHScompliant with exemption
RoHS exemption6c: Copper alloy with a mass fraction of up to 4% lead, 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors
China-RoHSwww.beckhoff.com/china-rohs-io
CA Prop65www.beckhoff.com/prop65
DisclaimerThis statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply.
Material compliance | SCIPSCIP No.
IP5209-B3182891ebe2-fbf0-4948-b1db-f7a3a34cb218
IP5209-B318-1000b45fbc9f-ac6b-483c-8018-de7f9758682b