The EL1382 digital input terminal analyzes the input signal from thermistor sensors with the help of a current loop and a voltage of < 5 V. The EtherCAT Terminal contains two channels. The EL1382 is a monitoring device for thermal machine protection by PTC sensors and for the direct monitoring of motors, bearings and plants. In addition to the switching state, open circuit or short circuit is also detected. The LEDs display the signal states or any error states.
Special features:
- suitable as a monitoring device for thermal machine protection, e.g., PTC sensors
- direct monitoring of motors, bearings and plants
- possibility to diagnose open circuit and short circuit
Product status:
regular delivery
Product information
| Technical data | EL1382 |
|---|---|
| Connection technology | 2-wire |
| Specification | thermistor PTC |
| Number of inputs | 2 |
| Nominal voltage | 24 V (-15%/+20%) |
| Signal voltage “0” | ≤ 1.5 kΩ |
| Signal voltage “1” | ≥ 3 kΩ |
| Signal “0” release | ≤ 1.5 kΩ |
| Signal “1” excess temperature | ≥ 3 kΩ |
| Sensor voltage | ≤ 5 V |
| Diagnostics | open-circuit monitoring > 12 kΩ, short-circuit diagnostic < 25 Ω |
| Input filter | typ. 30 ms |
| Distributed clocks | – |
| Current consumption E-bus | typ. 150 mA |
| Electrical isolation | 500 V (E-bus/field potential) |
| Special features | monitoring device for thermal machine protection |
| Weight | approx. 55 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring level | for all ESxxxx terminals |
| Approvals/markings | CE, UL |
| Housing data | EL-12-8pin | ES-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL1382 | EtherCAT Terminal, 2-channel digital input, thermistor, 30 ms |
| ES1382 | EtherCAT Terminal, 2-channel digital input, thermistor, 30 ms, pluggable wiring level |
Loading content ...
| Material compliance | EL1382 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |