The EL3202 analog input terminal facilitates the direct connection of two resistance sensors. The measured resistance value can either be output directly in ohms or transformed into a temperature. If the temperature at the measuring point is of interest, the conversion from resistance to temperature can be carried out in the terminal according to various sensor characteristics (Pt100, Pt1000, NI120, NI1000, KTY types, etc.). The EL3202 can operate sensors in 2- and 3-wire technology, for the 2-wire connection an external bridge is necessary. The EtherCAT Terminals indicate their measurement capability by means of light emitting diodes and status bits in the EtherCAT process image.
Product status:
regular delivery
Product information
| Technical data | EL3202 |
|---|---|
| Number of inputs | 2 |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Input filter cut-off frequency | typ. 1 kHz |
| Sensor type | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…4 kΩ), KTY sensors (types see documentation) |
| Connection technology | 2- or 3-wire (default: 2-wire) |
| Conversion time | approx. 85 ms default setting, 2…800 ms configurable |
| Measuring current | < 0.5 mA (load-dependent) |
| Temperature range | -200…+850°C (Pt sensors); -60…+250°C (Ni sensors) |
| Resolution | 0.1°C per digit |
| Measurement error/uncertainty | < ±0.5°C for Pt sensors |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption E-bus | typ. 190 mA |
| Current consumption power contacts | – |
| Bit width in the process image | 2 x 32 bit RTD input |
| Special features | integrated digital filter, limit value monitoring, variable connection technology |
| Weight | approx. 60 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Pluggable wiring level | for all ESxxxx terminals |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Housing data | EL-12-8pin | ES-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL3202 | EtherCAT Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit |
| ES3202 | EtherCAT Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit, pluggable wiring level |
Loading content ...
| Material compliance | EL3202 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |