The IP5009 SSI interface module allows an SSI encoder to be connected directly. The encoder is powered via the SSI interface. The interface circuit generates a pulse for reading the encoder and makes the incoming data stream available to the controller as a data word in the process image. The module can optionally provide the data as binary numbers or as a binary gray code. Various operating modes, transmission frequencies and bit widths can be permanently stored in a control register.
Product status:
regular delivery
Product information
| Technical data position measurement | IP5009-Bxxx |
|---|---|
| Connection technology | M23 connector with outer thread, 12-pin |
| Number of channels | 1 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Signal input | difference signal (RS485) |
| Encoder supply | 24 V DC, from load voltage |
| Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
| Data transfer rates | variable up to 1 MHz, 250 kHz default |
| Serial input | 24 bits (adjustable) |
| Data direction | read |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Current consumption from US (without sensor current) | see documentation |
| Bit width in the process image | input: 1 x 32 bit data (1 x 8 bit control/status optional) |
| Electrical isolation | depends on the bus system |
| Technical data | IP5009-B318 |
|---|---|
| Configuration | via KS2000 or the controller, DP-V1 extensions are supported |
| Data transfer rates | automatic detection up to 12 Mbaud |
| Bus interface | 1 x M12 socket, 5-pin, 1 x M12 plug, 5-pin (tee-connector integrated), B-coded |
| Data transfer medium | shielded copper cable, 2 x 0.25 mm² |
| Power supply | control voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Box supply current | 85 mA + current consumption of sensors, max. 0.5 A |
| Auxiliary power current | according to I/O type |
| Electrical isolation | control voltage/fieldbus: no, control voltage/inputs or outputs: according to I/O type |
| Data transfer time | approx. 0.5 ms with 10 stations each with 32 bit input and output |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL |
| Housing data | XXL housing |
|---|---|
| Dimensions (W x H x D) | 30 mm x 210 mm x 26.5 mm |
| Material | PA6 (polyamide) |
| Installation | 2 fixing holes 3.5 mm diameter for M3 |
| Accessories | |
|---|---|
| ZS5300-0003 | Mounting plate for Coupler Box, zinc-coated steel sheet, 270 mm x 30 mm x 1.5 mm |
| Material compliance | IP5009-B318 |
|---|---|
| CAS No. | 7439-92-1, 556-67-2, 115-86-6 |
| REACH SVHC | Lead, Octamethylcyclotetrasiloxane, Triphenyl phosphate |
| REACH Annex XVII | compliant |
| REACH Annex XIV | compliant |
| SCIP No. | SCIP submission in progress |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 6c: Copper alloy with a mass fraction of up to 4% lead, 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |