OdpniPripniZapri

EPX3184-0022 | EtherCAT Box, 4-channel analog input, current, 4…20 mA, 16 bit, single-ended, M12, HART, Ex i

EPX3184-0022 | EtherCAT Box, 4-channel analog input, current, 4…20 mA, 16 bit, single-ended, M12, HART, Ex i

EPX3184-0022 | EtherCAT Box, 4-channel analog input, current, 4…20 mA, 16 bit, single-ended, M12, HART, Ex i

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
Top view 
EPX3184-0022 | EtherCAT Box, 4-channel analog input, current, 4…20 mA, 16 bit, single-ended, M12, HART, Ex i

EPX3184-0022 | EtherCAT Box, 4-channel analog input, current, 4…20 mA, 16 bit, single-ended, M12, HART, Ex i

The EPX3184-0022 analog EtherCAT Box allows intrinsically safe HART-capable field devices from hazardous areas of zones 0/20 and 1/21 to be directly connected. It supplies measuring transducers located in the field and transmits their analog measuring signals to the automation device under electrical isolation. The EtherCAT Box indicates the status of the HART communication via LEDs and signals any communication errors.

 

The HART (Highway Addressable Remote Transducer) protocol enables two-way communication through digital data transfer via the analog 4...20 mA wiring. In this way, further data can be exchanged with the field device via the superimposed digital signal, in addition to the analog current signal.

 

HART communication can also be used for the FDT/DTM concept. The TwinCAT FDT Container enables field device DTMs to be directly integrated into TwinCAT Engineering. This means that field device configuration and diagnostics are already available in the development environment.

Product status:

regular delivery

Product information

Technical dataEPX3184-0022
ProtocolEtherCAT
Bus interface2 x M8 socket, 4-pin, a-coded, shielded
SpecificationHART (version 7)
Number of inputs4 (single-ended)
Input connectionsM12 x 1, 5-pin, a-coded
Connection method2-wire
Signal current4…20 mA
Internal resistancetyp. 250 Ω
Resolution16 bit (incl. sign)
Measurement error/ uncertainty< ±0.3% (relative to full scale value)
Conversion timetyp. 1 ms
Input filter limit frequency16 Hz
Nominal voltage24 V DC
Distributed clocksyes
Input filterconfigurable
Sensor supplyfrom load supply voltage UP
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Current consumption from US50 mA
Special featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoring, NE43 NAMUR
Weightapprox. 250 g
Operating/storage temperature-25…+70°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL, Ex, IECEx (in preparation)
Housing data16 x M8, 8 x M12
Dimensions (W x H x D)60 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4