AyırSabitleKapat

EP3182-1002 | EtherCAT Box, 2-channel analog input + 2-channel digital output, multi-function, ±10 V, 0/4…20 mA, 16 bit, single-ended, M12

EP3182-1002 | EtherCAT Box, 2-channel analog input + 2-channel digital output, multi-function, ±10 V, 0/4…20 mA, 16 bit, single-ended, M12

EP3182-1002 | EtherCAT Box, 2-channel analog input + 2-channel digital output, multi-function, ±10 V, 0/4…20 mA, 16 bit, single-ended, M12

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | Sensor Supply UP
2 | Analog In
3 | Digital Out
4 | GNDP
5 | Shield
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
Top view 
I/O connection 
Connector assignment 
EP3182-1002 | EtherCAT Box, 2-channel analog input + 2-channel digital output, multi-function, ±10 V, 0/4…20 mA, 16 bit, single-ended, M12

EP3182-1002 | EtherCAT Box, 2-channel analog input + 2-channel digital output, multi-function, ±10 V, 0/4…20 mA, 16 bit, single-ended, M12

Measurement technology easily configured: Analog EtherCAT input terminals.

Measurement technology simply integrated: With the analog EtherCAT Terminals.

Measurement technology easily configured: Analog EtherCAT input terminals.

Measurement technology simply integrated: With the analog EtherCAT Terminals.

The EP3182-1002 EtherCAT Box has two analog inputs which can be individually parameterized, so that they process signals either in the -10/0 to +10 V or the 0/4 to 20 mA range. The voltage or input current is digitized with a resolution of 16 bits, and is transmitted (electrically isolated) to the higher-level automation device. The two input channels are single-ended inputs and possess a common, internal ground potential. The input filter and therefore the conversion times are configurable in a wide range. If required, the inputs can be scaled differently, and automatic limit monitoring is also available. EtherCAT is used for parameterization purposes. The parameters are stored in the module.

In addition, the EP3182-1002 has two digital outputs to connect binary control signals from the controller to the actuators at the process level. These two outputs (sink/source type) are intended to switch logic inputs or outputs with a minimum impedance of 10 kΩ (e.g. reset inputs of digital sensors). They handle load currents of up to 2 mA, are short-circuit proof and indicate their status through light emitting diodes.

The signals are connected via the two M12 connectors.