M12 plug field assembly for sensor cables with temperature compensation element.
Pt1000 for temperature compensation measurement
The M12 plug is suitable for temperature compensation for the EP3314, IE3312 and IP3312-Bxxx fieldbus box modules. The plug contains an integrated Pt1000 element. The measuring thermocouple can be connected via screw terminals in the plug. The temperature at the transition from the thermocouple to the screw terminal is measured via the Pt1000 element. This temperature is automatically compensated in the module.
Product status:
regular delivery
Product information
| Technical data | ZS2000-3712 |
|---|---|
| Shielding | no |
| Installation size | M12 |
| Connector type | plug |
| Contact type | male |
| Number of positions (face) | 5-pin |
| Coding | A‑coded |
| Rated current | 4 A at 40°C (according to IEC 61076-2-101) |
| Rated voltage | 30 V |
| Recommended torque, nut | 0.6 Nm |
| Mating cycles | ≥ 100 (according to IEC 60512-9a) |
| Wire termination | screw connection |
| Max. wire cross-section | max. 0.75 mm² (AWG18) |
| Max. cable outer diameter | 3.0…6.5 mm |
| Material | plastic |
For further technical details, please refer to the data sheet.

| A1 | ~60.00 mm |
| A2 | Ø 20.00 mm |
| Ordering information | |
|---|---|
| ZS2000-3712 | plug, field assembly, sensor, IP65/67, M12, straight, male, 5-pin, A-coded, with cold junction compensation |
| Material compliance | ZS2000-3712 |
|---|---|
| CAS No. | 7439-92-1 |
| REACH SVHC | Lead |
| REACH Annex XVII | compliant |
| REACH Annex XIV | compliant |
| SCIP No. | 471a1762-e274-40a6-978e-ba0916bdcda5 |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 6c: Copper alloy with a mass fraction of up to 4% lead |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |