The EL4072, EL4074, and EL4078 analog output terminals output 10 V/20 mA standard signals with 16-bit resolution and up to 2000 values per second. Each channel can be parameterized individually via the controller/TwinCAT. All common standard signals in the range of ±10 V and ±20 mA can be output per channel – for example, 0…10 V and 4…20 mA. Each channel signals a short circuit for voltage output or a wire break for current output. The current outputs can also drive high burden resistors.
The outputs are designed as single-ended, which means that one connection point of each channel is already connected in the terminal to +24 V or GND and no longer needs to be wired separately.
Special features:
- combined output terminal: 10 V/20 mA
- 107% measurement/output range
- high output power at 20 mA: load up to 300 Ω
- 2 ksps conversion rate per channel for standard automation tasks
- output diagnosis (short circuit at voltage output, wire break at current output)
Product status:
regular delivery
Product information
| Technical data | Analog output |
|---|---|
| Number of outputs | 8 |
| Wiring | 2-wire |
| Ground reference (input) | single-ended |
| Max. sampling rate | min. 500 µs (max. 2 ksps) per channel |
| Sampling type | multiplex, approx. 25 µs delay between channels n/n+1 |
| Load | voltage: > 2 kΩ (short-circuit proof) current: < 300 Ω |
| Output range, nominal | -10/0…+10 V | -20/0/+4…+20 mA |
| Output range, technical | -10.73…+10.73 V | -21.47…+21.47 mA |
| Resolution | 16 bit (incl. sign) |
| Measurement error/uncertainty | typ. < ±0.07%AEW (voltage and current, at 25°C ±5°C, otherwise < ±0.1%) |
| Electrical isolation | Channel/channel | no |
| Technical data | General |
|---|---|
| Power supply | via power contacts, 24 V DC (-15%/+20%) |
| Distributed clocks | – |
| Electrical isolation | channel/E-bus: functional separation 707 V DC type test |
| Current consumption power contacts | typ. 60 mA (required for operation of the outputs, specification at full load, additional current requirement at +24 V/0 V connected loads) |
| Current consumption E-bus | typ. 180 mA |
| Special features | U/I parameterizable, ExtendedRange 107%, output diagnosis |
| Weight | approx. 65 g |
| Operating temperature | -25…+55°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
| Housing data | EL-12-16pin |
|---|---|
| Design form | HD (High Density) housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductors (s): direct plug-in technology; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm² |
| Connection cross-section AWG | s*: AWG28…16, st*: AWG22…16, f*: AWG26…19 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
*s: solid wire; st: stranded wire; f: with ferrule
Loading content ...
| Material compliance | EL4078 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |