The EL4172 analog output terminal outputs 10 V/20 mA standard signals with 16-bit resolution and up to 10,000 values per second – even with distributed clocks if necessary. Each channel can be parameterized individually using the control/TwinCAT and supports all common standard signals in the ±10 V and ±20 mA range, such as 4...20 mA. The current outputs can drive high load resistances and are equipped with 24 V/0 V contacts to supply actuators. With an extended output range of ±107%, unconventional setpoints can also be output – for error reporting purposes, as an example.
Additional functions make the EL4172 a versatile solution for demanding analog tasks. It offers electrically isolated outputs that can control inputs without a ground reference. Each channel can be switched off separately with high resistance. Voltage and current monitoring enable the U/I values that are actually flowing to be fed back as process data, allowing real-time diagnosis of the load and wiring (to identify short circuits, for example). It supports 4-wire operation (Kelvin method), which compensates for any voltage drops across the supply lines during voltage mode. Diagnostics are also integrated for the power contact voltage.
Product status:
product announcement | estimated market release 4th quarter 2026
Product information
| Technical data | Analog output |
|---|---|
| Number of outputs | 2 |
| Wiring | 2-wire, 4-wire |
| Ground reference (input) | differential |
| Max. sampling rate | min. 100 µs (max. 10 ksps) per channel |
| Sampling type | synchronous |
| Load | voltage: > 2 kΩ (short-circuit proof) current: < 750 Ω |
| Output range, nominal | -10/0…+10 V | -20/0/+4…+20 mA |
| Output range, technical | -10.73…+10.73 V | -21.47…+21.47 mA |
| Resolution | 16 bit (incl. sign) |
| Measurement error/uncertainty | typ. < ±0.07%AEW (voltage and current, at 25°C ±5°C, otherwise < ±0.1%) |
| Electrical isolation | Channel/channel | yes |
| Technical data | General |
|---|---|
| Power supply | via power contacts, 24 V DC (-15%/+20%) |
| Distributed clocks | yes |
| Electrical isolation | channel/bus and channel/channel: functional separation 707 V DC type test |
| Current consumption power contacts | typ. 60 mA (required for operation of the outputs, specification at full load, additional current requirement at +24 V/0 V connected loads) |
| Current consumption E-bus | typ. 90 mA |
| Special features | U/I parameterizable, ExtendedRange 107%, output diagnosis |
| Weight | approx. 65 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
| Housing data | EL-12-16pin |
|---|---|
| Design form | HD (High Density) housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductors (s): direct plug-in technology; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm² |
| Connection cross-section AWG | s*: AWG28…16, st*: AWG22…16, f*: AWG26…19 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
*s: solid wire; st: stranded wire; f: with ferrule
Loading content ...
| Material compliance | EL4172 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |
Loading content ...
© Beckhoff Automation 2026 - Terms of Use