DetachFixClose

EL3403-0010 | 3-phase power measurement terminal

EL3403-0010 | 3-phase power measurement terminal

EL3403-0010 | 3-phase power measurement terminal

Run LED
L1 OK
L2 OK
L3 OK
Phase OK
L1 error
L2 error
L3 error
L1
L2
L3
N
IL1
IL2
IL3
IN
Top view 
Contact assembly 
EL3403-0010 | 3-phase power measurement terminal

EL3403-0010 | 3-phase power measurement terminal

The EL3403-0010 EtherCAT Terminal enables the measurement of all relevant electrical data of the supply network. The voltage is measured via the direct connection of L1, L2, L3 and N. The current of the three phases L1, L2 and L3 is fed via simple current transformers. All measured currents and voltages are available as root-mean-square values. In the EL3403-0010 version, the effective power and the energy consumption for each phase are calculated. The root-mean-square value of voltage U, current I and the effective power P, apparent power S, reactive power Q, frequency F and phase shift angle cos φ can be derived. The EL3403-0010 provides a comprehensive network analysis and an energy management option.

Product status:

Regular delivery (not recommended for new projects) | recommended alternative: EL3443