The KM3701 pressure measuring terminal enables direct measurement of pressure differences between two hose connections. The pressure difference is available in the fieldbus as a 16 bit value and can be measured between any points up to an ambient pressure of 10 bar. The status LEDs indicate proper function or errors such as over-range.
Product status:
Regular delivery
Product information
- Technical Data
- Ordering Information
- Software
- Documentation and Downloads
- Beckhoff Information System
- Application Notes
- Related products
Technical data | KM3701 |
---|---|
Technology | differential pressure measurement |
Number of inputs | 1 (differential pressure) |
Measuring error | 3 % (relative to full scale value) |
Measuring range | -100…+100 hPa (-100…+100 mbar) |
Max. overload | 500 hPa (500 mbar) differential, 5000 hPa (5 bar) to ambient |
Resolution | 0.1 hPa (0.1 mbar) per digit |
Measuring speed | 5 ms typ. |
Current consumption power contacts | – (no power contacts) |
Current consumption K-bus | typ. 15 mA |
Bit width in the process image | 3 byte input/output |
Medium | non-aggressive gases |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL |
Housing data | KL-24 |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 24 mm x 100 mm x 52 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | specific push-in connection |
Ordering information | |
---|---|
KM3701 | Bus Terminal module, 1-channel analog input, differential pressure, ±100 hPa (±100 mbar) |
KM3701-0340 | differential pressure up to 340 hPa |