SoltarAdjuntarCerrar

Oficina central México
Beckhoff Automation, S.A. de C.V.

Boulevard Manuel Ávila Camacho 2610, Torre B, Piso 9, Colonia Valle de los Pinos, Tlalnepantla de Baz
Estado de México CP 54040, México

+52 55 75998058
mexico@beckhoff.com
www.beckhoff.com/es-mx/

EPP4174-0002 | EtherCAT P Box, 4-channel analog output, multi-function, ±10 V, 0/4…20 mA, 16 bit, differential, M12

EPP4174-0002 | EtherCAT P Box, 4-channel analog output, multi-function, ±10 V, 0/4…20 mA, 16 bit, differential, M12

EPP4174-0002 | EtherCAT P Box, 4-channel analog output, multi-function, ±10 V, 0/4…20 mA, 16 bit, differential, M12

EtherCAT P signal input
EtherCAT P signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
1 | Tx+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
1 | Output +
2 | +24 V DC UP
3 | Output -
4 | GNDP
5 | Shield
Top view 
I/O connection 
Connector assignment 
EPP4174-0002 | EtherCAT P Box, 4-channel analog output, multi-function, ±10 V, 0/4…20 mA, 16 bit, differential, M12

EPP4174-0002 | EtherCAT P Box, 4-channel analog output, multi-function, ±10 V, 0/4…20 mA, 16 bit, differential, M12

EtherCAT P: The one cable solution – One step closer to automation without control cabinets

EtherCAT P: The one cable solution – One step closer to automation without control cabinets

The EPP4174-0002 EtherCAT P Box has four analog outputs which can be individually parameterized, so that they generate signals either in the -10 to +10 V or the 0/4 to 20 mA range. The voltage or output current is supplied to the process level with a resolution of 15 bit (default), and is electrically isolated. The output scaling can be changed if required.

Ground potential for the four output channels is common with the 24 V DC supply. The analog actuators are supplied from the load voltage (freely selectable up to 30 V DC). The applied load voltage is available for actuator supply of further EtherCAT P Box modules.

Product status:

regular delivery

Product information

Technical dataEPP4174-0002
ProtocolEtherCAT
Bus interface2 x M8 socket, P-coded, shielded
Number of channels4 analog outputs
Output connectionsM12 x 1, 5-pin, a-coded
Signal type-10/0…+10 V | 0/4…20 mA, parameterizable per channel
Nominal voltage24 V DC (-15%/+20%)
Load> 5 kΩ | < 500 Ω
Resolution16 bit
Conversion time~ 40 µs
Measurement error/ uncertainty< 0.1% (relative to full scale value)
Actuator supplyfrom the auxiliary voltage UP
Electrical isolation500 V
Current consumption from UStyp. 100 mA
Special featurescurrent or voltage parameterizable per channel
Weightapprox. 165 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing data8 x M8, 4 x M12
Dimensions (W x H x D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3

Loading content ...

Loading content ...

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use