SoltarAdjuntarCerrar

Oficina central México
Beckhoff Automation, S.A. de C.V.

Boulevard Manuel Ávila Camacho 2610, Torre B, Piso 9, Colonia Valle de los Pinos, Tlalnepantla de Baz
Estado de México CP 54040, México

+52 55 75998058
mexico@beckhoff.com
www.beckhoff.com/es-mx/

EP6224-3022 | EtherCAT Box, 4-channel communication interface, IO-Link, master, Class B, M12

EP6224-3022 | EtherCAT Box, 4-channel communication interface, IO-Link, master, Class B, M12

EP6224-3022 | EtherCAT Box, 4-channel communication interface, IO-Link, master, Class B, M12

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Labeling areas
Power supply feed
Power supply downstream
connection
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | L+
2 | P24
3 | L-
4 | C/Q
5 | N24
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
Top view 
I/O connection 
Connector assignment 
EP6224-3022 | EtherCAT Box, 4-channel communication interface, IO-Link, master, Class B, M12

EP6224-3022 | EtherCAT Box, 4-channel communication interface, IO-Link, master, Class B, M12

From the IO-Link sensor into the cloud

From the IO-Link sensor into the cloud

The EP6224-3022 IO-Link module enables connection of up to four IO-Link devices, e.g. actuators, sensors or combinations of both. A point-to-point connection is used between the terminal and the device. The module is parameterized via the EtherCAT master. IO-Link is designed as an intelligent link between the fieldbus level and the sensor, wherein parameterization information can be exchanged bidirectionally via the IO-Link connection. The parameterization of the IO-Link devices with service data can be done from TwinCAT via ADS or very conveniently via the integrated IO-Link configuration tool.

In the standard setting, the EP6224-3022 functions as a 4-channel input terminal, 24 V DC, which communicates with connected IO-Link devices, parameterizes them and, if necessary, changes their operating mode.

Product status:

regular delivery

Product information

Technical dataEP6224-3022
ProtocolEtherCAT
Bus interface2 x M8 socket, 4-pin, a-coded, shielded
Data transfer rates4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Specification versionIO-Link V1.1, Class B
IO-Link interfaces4
Connection methodM12 socket, 5-pin, a-coded
Nominal voltage24 V DC (-15%/+20%)
IO-Link sensor supply L+24 V DC, 1.4 A per port, ∑ 4.0 A for 4 ports
IO-Link extra power P2424 V DC, 2.0 A per port, ∑ 4.0 A for 4 ports
Current consumption from UStyp. 130 mA + load
Electrical isolation500 V
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Distributed clocksyes
Weightapprox. 250 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing data16 x M8, 8 x M12
Dimensions (W x H x D)60 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4

Loading content ...

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use