The EL3022 analog input terminal processes signals in the range between 4 and 20 mA. The current is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the EtherCAT Terminal have differential inputs and possess a common, internal ground potential. The EL3022 combines two channels in one housing. An open lead or overload condition are detected. The terminal status is relayed to the controller via the E-bus. The EtherCAT Terminal indicates its signal state by means of light emitting diodes. The error LEDs indicate an overload condition and a broken wire.
Product status:
regular delivery
Product information
| Technical data | EL3022 |
|---|---|
| Number of inputs | 2 (differential) |
| Power supply | via the E-bus |
| Signal current | 4…20 mA |
| Distributed clocks | – |
| Internal resistance | typ. 85 Ω + diode voltage |
| Input filter cut-off frequency | 1 kHz |
| Common mode voltage UCM | max. 10 V |
| Conversion time | 0.625 ms default setting, configurable, multiplex |
| Resolution | 12 bit (16 bit presentation incl. sign) |
| Measurement error/uncertainty | < ±0.3% (relative to full scale value) |
| Surge voltage resistance | max. 35 V |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption E-bus | typ. 130 mA |
| Current consumption power contacts | – |
| Bit width in the process image | inputs: 8 byte |
| Special features | standard and compact process image, activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 55 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Pluggable wiring level | for all ESxxxx terminals |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Housing data | EL-12-8pin | ES-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL3022 | EtherCAT Terminal, 2-channel analog input, current, 4…20 mA, 12 bit, differential |
| ES3022 | EtherCAT Terminal, 2-channel analog input, current, 4…20 mA, 12 bit, differential, pluggable wiring level |
Loading content ...
| Material compliance | EL3022 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |
Loading content ...
Loading content ...
© Beckhoff Automation 2026 - Terms of Use