EL6821 | EtherCAT Terminal, 1-channel communication interface, DALI-2, master/power supply

Image similar, may contain optional accessories
EL6821 | EtherCAT Terminal, 1-channel communication interface, DALI-2, master/power supply

EL6821 | EtherCAT Terminal, 1-channel communication interface, DALI-2, master/power supply

Run
Send
+24 V power
Input 1
Device error
Receive
DALI power
Input 2
+24 V DC
Input 1
DALI+
DALI-
0 V
Input 2
DALI+
DALI-
EL6821 | EtherCAT Terminal, 1-channel communication interface, DALI-2, master/power supply

EL6821 | EtherCAT Terminal, 1-channel communication interface, DALI-2, master/power supply

The EL6821 allows up to 64 DALI-/DALI-2 slaves and 64 DALI-2 input devices to be connected. The TwinCAT 3 System Manager makes it easy to configure and parameterize DALI devices. Programming is performed exclusively via TwinCAT 3 function blocks. The EL6821 contains an integrated DALI bus power supply that can be switched off. The galvanically isolated input voltage of 24 V DC must be supplied via the EL9562 power supply terminal or via the PS1111-2402-0002, PS1111-2403-0000, or PS1111-2403-0002 power supplies in order to comply with the certification requirements.

 

The EL6821 is certified in accordance with the DALI-2 standard.

DALI-2 Part 101, version 2.0 and Part 103, version 2.0

Product status:

regular delivery

Product information

Technical dataEL6821
TechnologyDALI-2
Slaves/groupsmax. 64 DALI control gears (ballasts) and max. 64 control devices (input devices/application controller)
Data transfer channels1
Data transfer standardDALI + DALI-2
Transmission rate1200 baud
Electrical isolation500 V (E-bus/DALI-bus)
Current consumption power contacts
Current consumption E-bustyp. 80 mA
Input voltage24 V DC (-15%/+20%)
Insulation voltageDALI-bus/E-bus: 1,500 V DC
DALI power supplymax. 250 mA (can be switched off)
Guaranteed output current220 mA
Surge voltage resistanceconstant load 275 V ACrms
Special features2 digital inputs for simplified installation; TwinCAT library: TwinCAT PLC DALI
Weightapprox. 80 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE
Housing dataEL-12-8pin
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxxx series
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG28…14,
st*: AWG28…14,
f*: AWG26…16
Stripping length8…9 mm
Current load power contactsImax: 10 A
Dimensions (W x H x D)12 mm x 100 mm x 68 mm

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Material complianceEL6821
REACH SVHCno
POPcompliant
RoHScompliant with exemption
RoHS exemption7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors
China-RoHSwww.beckhoff.com/china-rohs-io
CA Prop65www.beckhoff.com/prop65
DisclaimerThis statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply.

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2026 - Terms of Use