EC1100 | EtherCAT Coupler, RJ45, angled, push-in

Image similar, may contain optional accessories
EC1100 | EtherCAT Coupler, RJ45, angled, push-in

EC1100 | EtherCAT Coupler, RJ45, angled, push-in

Image similar, may contain optional accessories
EC1100 | EtherCAT Coupler, RJ45, angled, push-in

EC1100 | EtherCAT Coupler, RJ45, angled, push-in





US 24 V | UP 24 V
E-Bus Link/Act | Run
X1 Link/Act
X2 Link/Act


Infeed US 24 V | 0 V


Infeed UP 24 V


Infeed UP 0 V


X1 In


X2 Out
EC1100 | EtherCAT Coupler, RJ45, angled, push-in

EC1100 | EtherCAT Coupler, RJ45, angled, push-in

EC1100 | EtherCAT Coupler, RJ45, angled, push-in

EC1100 | EtherCAT Coupler, RJ45, angled, push-in

The EC1100 EtherCAT Coupler is the link between the EtherCAT protocol at fieldbus level and the EtherCAT Terminals. Due to the angled RJ45 sockets, the cable can be fed directly into the cable channel without the need for larger bending radii. The coupler converts the passing telegrams from Ethernet 100BASE-TX to E-bus signal representation. A station consists of a coupler and any number of EtherCAT Terminals that are automatically detected and individually displayed in the process image.

 

Special features:

  • connection technology: 2 x RJ45 sockets, angled
  • connection lengths: up to 100 m
  • number of EtherCAT Terminals in the overall system: up to 65,535

 

The EC1100 has two RJ45 sockets. The upper Ethernet interface is used to connect the coupler to the network; the lower socket serves for the optional connection of further EtherCAT devices in the same segment. In addition, an EtherCAT junction or an EtherCAT extension can be used for the extension or for setting up a line or star topology.

 

The system and field supply, each 24 V DC, is provided directly at the coupler. The attached EtherCAT Terminals are supplied with the current required for communication from the supplied system voltage. The coupler supplies a maximum of 5 V and 2 A. If higher current is required, power supply terminals such as the ED9410 have to be integrated. The field supply is forwarded to the individual I/O components via the power contacts with up to 10 A.

 

In the EtherCAT network, the EC1100 can be installed anywhere in the Ethernet signal transmission section (100BASE-TX) – except directly at the switch. The EK9000 and EK1000 couplers are suitable for use at the switch.

 

The EC-series EtherCAT Couplers have push-in connection technology which makes wiring easy and tool-free.

Product status:

product announcement | estimated market release 2nd quarter 2026

Product information

GeneralEC1100
Internal communication protocolEtherCAT
Communication interfaceEC1100
Number of ports2
FunctionCoupling of EtherCAT Terminals to 100BASE-TX EtherCAT networks
ProtocolEtherCAT
Transmission typehalf or full duplex
Data transfer mediumEthernet/EtherCAT cable (at least Cat.5), shielded
Transmission rate100 Mbit/s
Delaytyp. 1 µs
Number of devicesmax. 65,534
Cable length | Point-to-pointmax. 100 m
ID switchno
Connection technologyRJ45
Connection technology | Contact typesocket
XFCEC1100
Distributed clocksno
Timestampno
Oversamplingno
Supply and electrical isolationEC1100
Electronics | Supply voltage24 V DC (-15 %/+20 %)
Electronics | Current consumptiontyp. 70 mA + (∑ E-bus current consumption/4)
E-bus | Output currentmax. 2 A
Power contacts | Input voltagemax. 24 V DC (+20 %)
Power contacts | Current carrying capacitymax. 10 A
Power contacts | Current consumptionload-dependent
Power contacts | Output voltagecorresponds to Power contacts | input voltage
Power contacts | Output currentmax. 10 A
Environmental conditionsEC1100
Operating temperature0…55°C
Storage temperature-25…+85°C
Relative humidity95%, no condensation
Installation positionvariable
Standards and approvalsEC1100
Vibration resistanceconforms to EN 60068-2-6
Shock resistanceconforms to EN 60068-2-27
EMC immunityconforms to EN 61000-6-2
EMC emissionconforms to EN 61000-6-4
MarkingsCE
ApprovalscULus (in preparation)
Housing dataEC-40-8pin
Protection ratingIP20
Materialpolycarbonate
Dimesnions | Width (single)40 mm
Dimensions | Width (lined up)40 mm
Dimensions | Height100 mm
Dimensions | Depth65 mm
Installation | Terminal/back wallDIN rail, 35 mm (EN 60715)
Installation | Terminal/terminaldouble slot and key connection
Plug-in wiring levelno
Connection technologypush-in
Connection cross-section | Solid wire0.08…2.5 mm²
Connection cross-section | Stranded wire0.08…2.5 mm²
Connection cross-section | With ferrule0.14…1,5 mm²
Connection cross-section AWG | Solid wireAWG28…14
Connection cross-section AWG | Stranded wireAWG28…14
Connection cross-section AWG | With ferruleAWG26…16
Stripping length8…9 mm
Power contact | "+" (left)no
Power contact | "+" (rechts)yes
Power contact | "-" (left)no
Power contact | "-" (right)yes
Power contact | "⏚" (left)
no
Power contact | "⏚" (right)no
Insertion lock for power contact “⏚” no