SoltarAdjuntarCerrar

Oficina central México
Beckhoff Automation, S.A. de C.V.

Boulevard Manuel Ávila Camacho 2610, Torre B, Piso 9, Colonia Valle de los Pinos, Tlalnepantla de Baz
Estado de México CP 54040, México

+52 55 75998058
mexico@beckhoff.com
www.beckhoff.com/es-mx/

EPP2038-0001 | EtherCAT P Box, 8-channel digital output, 24 V DC, 2 A, M8, with diagnostics

EPP2038-0001 | EtherCAT P Box, 8-channel digital output, 24 V DC, 2 A, M8, with diagnostics

EPP2038-0001 | EtherCAT P Box, 8-channel digital output, 24 V DC, 2 A, M8, with diagnostics

EtherCAT P signal input
EtherCAT P signal output
M8 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
1 | Tx+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
1 | +24 V DC UP
3 | GND
4 | Output
2-wire
3-wire
Top view 
I/O connection 
Connector assignment 
EPP2038-0001 | EtherCAT P Box, 8-channel digital output, 24 V DC, 2 A, M8, with diagnostics

EPP2038-0001 | EtherCAT P Box, 8-channel digital output, 24 V DC, 2 A, M8, with diagnostics

EtherCAT P: The one cable solution – One step closer to automation without control cabinets

EtherCAT P: The one cable solution – One step closer to automation without control cabinets

The EPP2038-0001 EtherCAT P Box is designed for processing digital/binary signals. It connects the binary control signals from the automation device on to the actuators at the process level. The outputs can handle output currents up to 2.0 A max. Short-term overload is acceptable. The outputs are short-circuit proof. The sum current of all outputs is limited to 3 A.

The signal state of the channels is indicated by LEDs. With channel-based short-circuit and open-load/broken-wire detection, the EPP2038-0001 provides effective diagnostics to ensure reliable system availability. The signal connection is established via screw-type M8 connectors.

Product status:

regular delivery

Product information

Technical dataEPP2038-0001
ProtocolEtherCAT
Bus interface2 x M8 socket, P-coded, shielded
Number of outputs8
Output connectionsM8 x 1, 3-pin, a-coded
Load typeohmic, inductive, lamp load
Nominal output voltage24 V DC (-15%/+20%)
Max. output current2 A per channel, individually short-circuit proof, ∑ 3 A
Switching timestyp. TON: 200 µs, typ. TOFF: 200 µs
Short-circuit currenttyp. 15 A
Distributed clocks
Current consumption from UStyp. 100 mA
Auxiliary power currenttyp. 20 mA + load
Diagnosticsshort-circuit, open load detection (min. load > 200 mA)
Electrical isolation500 V
Weightapprox. 165 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing data8 x M8, 4 x M12
Dimensions (W x H x D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3