EPP3754-0002 | EtherCAT P Box, 4-channel analog input, multi-function, M12New

Image similar, may contain optional accessories
EPP3754-0002 | EtherCAT P Box, 4-channel analog input, multi-function, M12

EPP3754-0002 | EtherCAT P Box, 4-channel analog input, multi-function, M12

EtherCAT P signal input
EtherCAT P signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
1 | Tx+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
1 | +Uv
2 | Input +
3 | -Uv
4 | Input -
5 | Shield
EPP3754-0002 | EtherCAT P Box, 4-channel analog input, multi-function, M12

EPP3754-0002 | EtherCAT P Box, 4-channel analog input, multi-function, M12

The EPP3754-0002 EtherCAT P Box has four analog multi-functional inputs, which can be parameterized individually and extensively:

 

  • voltage measurement: -10…+10 V, 0...10 V
  • current measurement: ±20 mA, 4...20 mA, 0...20 mA
  • resistance measurement: 20 Ω…4 kΩ in 2-/3-/4-wire connection
  •  RTD measurement in 2-/3-/4-wire connection
  • thermocouple measurement

 

The measured values are digitized with a 16-bit resolution and transmitted electrically isolated to the higher-level automation device. The input filters and their associated conversion times are configurable in a wide range. The inputs can, if required, be scaled differently, and automatic limit value monitoring is also available. EtherCAT is used for parameterization purposes. The EtherCAT P Box can be used universally for a wide range of measurement tasks thanks to the flexible parameter settings.

Product status:

product announcement | estimated market release 4th quarter 2025

Product information

Technical dataGeneral
ProtocolEtherCAT
Bus interface2 x M8 socket, P-coded, shielded
Number of inputs4
Input connectionsM12 x 1, 5-pin, A-coded
Nominal voltage24 V DC (-15%/+20%)
Distributed clocksno
Current consumption from US~ 120 mA
Weightapprox. 200 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL (in preparation)
Technical dataAnalog input | Current
Conversion time~ 100 µs
Resolution16 bit (incl. sign)
Signal range | Nominal -20 mA/0/+4…+20 mA
Common mode voltage UCMmax. 12 V
Internal resistancetyp. 85 Ω
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable (free numeric filters)
Ground referencedifferential
Sensor supplyfrom control voltage, max. 180 mA per channel, short-circuit proof
Technical dataAnalog input | Voltage
Conversion time~ 100 µs
Resolution16 bit (incl. sign)
Signal type-10/0…+10 V
Common mode voltage UCMmax. 12 V
Internal resistance> 200 kΩ
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable (free numeric filters)
Ground referencedifferential
Sensor supplyfrom control voltage, max. 180 mA per channel, short-circuit proof
Technical dataAnalog input | Thermocouple
Conversion time~ 5 ms
Resolution16 bit (incl. sign)
Sensor typestype B, C, E, J, K, L, N, R, S, T, U, mV measurement
Signal type°C (thermocouple)
Common mode voltage UCMmax. 12 V
Internal resistance~ 1 MΩ
Measuring rangedepending on sensor type; preset value is type K, -100…+1370°C
Measurement error/uncertainty< ±0.3% for type K (relative to full scale value; further types see documentation)
Input filterconfigurable
Special featurescompensation for the cold junction
Technical dataAnalog input | Resistance thermometer (RTD)
Connection method2-, 3-, 4-wire
Conversion time~ 5 ms
Resolution16 bit (incl. sign)
Sensor typesPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000
Signal type°C (RTD)
Measuring range-200…+850 °C (Pt sensors); Pt100 default setting
Measurement error/uncertainty< ±0.5°C (Pt sensors in 4-wire connection)
Input filterconfigurable
Technical dataAnalog input | Resistance
Connection method2-, 3-, 4-wire
Conversion time~ 5 ms
Resolution16 bit (incl. sign)
Sensor typesresistance (20 Ω…4 kΩ)
Signal typeΩ
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable
Housing data8 x M8, 4 x M12
Dimensions (W x H x D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3