The EK1310 EtherCAT P power supply offers the option of converting from an EtherCAT segment, which is configured via an EtherCAT Coupler or an Embedded PC from the CX series, to EtherCAT P or extending an EtherCAT P network in line topology.
Special features:
- connection technology: 1 x P-coded M8 socket
- conversion from EtherCAT to EtherCAT P
- extension of an EtherCAT P network in line topology
Terminal points are used for the system and sensor supply US and the peripheral voltage for actuators UP for the EtherCAT P output. A connection to a further EtherCAT P segment or to individual EtherCAT P devices can be established via the P-coded M8 socket, which enables connection of an EtherCAT P cable with M8 connector.
Product status:
regular delivery
Product information
| Technical data | EK1310 |
|---|---|
| Task within EtherCAT system | conversion of the E-bus signals to 100BASE-TX Ethernet for feed-in in the EtherCAT P network |
| Data transfer medium | EtherCAT P cable, shielded, to 100BASE-TX EtherCAT P networks |
| Bus interface | 1 x M8 socket, shielded, screw type, P-coded |
| Power supply | external feed-in: 24 V DC (-15 %/+20 %) for US and UP |
| Sum current | max. 3 A per US and UP |
| Current consumption from US | typ. 3 mA |
| Current consumption from UP | typ. 3 mA |
| Current rating per port | max. 3 A per US and UP |
| Current consumption E-bus | typ. 110 mA |
| Electrical isolation | 500 V (supply voltage US/supply voltage UP/EtherCAT) |
| Storage temperature | -40…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL |
| Housing data | EK-44-8pin |
|---|---|
| Design form | compact terminal housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 44 mm x 100 mm x 68 mm |
*s: solid wire; st: stranded wire; f: with ferrule