EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combiNew

EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi

EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi

Run
Steady Ch1
Warning Ch1
Error Ch1
Input Ch1
Output Ch1
Power
Steady Ch2
Warning Ch2
Error Ch2
Input Ch2
Output Ch2
Power contact
+24 V
Power contact 0 V
+Input/Output Ch1
+UD1
+Uref1
+UV1
+UV2
+Uref2
+UD2
+Input/Output 2
-Input/Output Ch1
-UD1
-Uref1
-UV1
-UV2
-Uref2
-UD2
-Input/Output 2
Top view 
Contact assembly 
EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi

EL336x, EL336x-0100: EtherCAT Terminals for multi-channel measuring bridge detection with integrated power supply.

EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi

EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi

EL3362 | EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi

EL336x, EL336x-0100: EtherCAT Terminals for multi-channel measuring bridge detection with integrated power supply.

The EL3362 analog input terminal enables the direct connection of resistor bridges (strain gauges) or load cells using the 4-wire or 6-wire connection technique. It processes the ratio of the bridge voltage UD to the supply voltage UREF and outputs the final load value as a process value based on the terminal settings. This enables precise recording of weights, torques, and vibrations with a sampling rate of 10,000 samples per second.

 

The integrated bridge supply is generated from the 24 V of the power contacts, with a choice between 5 V and 10 V DC in the configuration.

 

The terminal also has a combined digital input/output per channel; the function for the digital connection point must be specified in the configuration. The digital input can be used for functions such as taring. The digital output can be switched on the basis of local evaluations in the terminal depending on the measured value of the resistance bridge.

Product status:

product announcement | estimated market release 3rd quarter 2024

Product information

Technical dataAnalog input
Number of inputs4, for 2 resistor bridge in full bridge technology
FunctionResistance bridge, strain gauge (SG), voltage measurement
Wiring4-wire, 6-wire
Ground reference (analog/encoder)differential
Max. sampling rate10 kSps
Sampling typesimultaneous
Internal resistance> 1 MΩ
Supported nominal sensitivity0.5…320 mV/V
Sensor supply10 V DC from power contacts
Measuring range, nominalUref: ±12 V | UD: ±4 V
Measuring range, technicalUref: ±12,84 V | UD: ±4,28 V
Resolution24 bit
Measurement error/uncertainty< ±0,05 %
Electrical isolation channel/channelno
Technical dataDigital input
Number of inputsmax. 1
Wiring1-wire
“0” signal voltage0…1.5 V
“1” signal voltage2.5…30 V
Input currenttyp. 3 mA
Technical dataDigital output
Number of outputsmax. 1
Wiring1-wire
Nominal voltage24 V DC (-15%/+20%)
Load typeohmic, inductive
Max. output current0.5 A
Reverse voltage protectionyes
Technical dataGeneral
Power supplyvia the E-bus
Electrical isolation channel/bus707 V DC (type test)
Current consumption power contactstyp. 30 mA, depends on UV
Current consumption E-bustyp. 90 mA
Distributed clocks
Special featuresintegrated sensor supply, digital inputs/outputs, specification of the digital output depending on the analog measurement
Weightapprox. 50 g
Operating/storage temperature0…+55°C/-25…+85°C
Relative humidity95%, no condensation
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE
Housing dataEL-12-16pin
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Connection cross-section AWGs*: AWG28…16,
st*: AWG22…16,
f*: AWG26…19
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule