The EL1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.
Product status:
regular delivery
Product information
| Technical data | EL1054 |
|---|---|
| Technology | NAMUR |
| Connection technology | 2-wire |
| Specification | NAMUR DC switching amplifier (IEC 60947-5-6) |
| Signal type | binary, current input for NAMUR sensors |
| Number of inputs | 4 |
| Open circuit voltage | typ. 8.2 V DC |
| Signal current “0” | ≤ 1.2 mA |
| Signal current “1” | ≥ 2.1 mA |
| Switching hysteresis | typ. 350 µA |
| Short-circuit current | typ. 7.8 mA |
| Fault detection | I ≤ 200 µA (cable break), I ≥ 7.0 mA (short circuit) |
| Max. switching frequency | 5 kHz (duty cycle 50%) |
| Internal resistance | according to I/V curve IEC 60947-5-6 |
| Distributed clocks | – |
| Supply voltage electronics | 24 V DC (via power contacts) |
| Current consumption E-bus | typ. 50 mA |
| Electrical isolation | 500 V (E-bus/field potential) |
| Special features | integrated reverse polarity protection |
| Weight | approx. 60 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring level | for all ESxxxx terminals |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Housing data | EL-12-8pin | ES-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL1054 | EtherCAT Terminal, 4-channel digital input, NAMUR |
| ES1054 | EtherCAT Terminal, 4-channel digital input, NAMUR, pluggable wiring level |
Loading content ...
| Material compliance | EL1054 |
|---|---|
| REACH SVHC | no |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-io |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |