The MR1307-0011-2242 is a 3-phase relay output including load current measurement. The load currents are output via three separate M12 connectors, each of which can switch up to 10 A max. and must not exceed 15 A in total.
Product status:
product announcement
Product information
Technical data | MR1307-0011-2242 |
---|---|
Product category | relay modules |
Category/version | relay output |
Channels | 3 |
Connection method | M12 |
Output voltage | 230/400 V AC 3~ |
Output current | 7 A per channel (∑ 15 A) |
Shutdown | yes |
Resolution | 16 bit |
Output | 3 kVA per channel |
Residual current measurement | no |
Change of rotation direction | no |
Supply voltage from backplane | 400…480 V AC |
Load type | ohmic, inductive |
Load current measurement | yes |
Measuring error | I: 1.25% referred to the measuring range end value |
Number of phases | 3 |
Sensor types | RTD/TC |
Fuse | replaceable |
Additional in-/outputs | 3 |
Baseplate interface | data and power connector |
Diagnostics | open-circuit detection, undervoltage |
Distributed clocks | yes |
Hot swap | yes |
TwinCAT version | TwinCAT 3 |
Weight | 2000 g |
Approvals/markings | CE, UL (in preparation) |
Housing data | R2S2T3 |
---|---|
Dimensions (W x H x D) | 70 mm × 240 mm × 112 mm |
Number of rows | 2 |
Number of slots | 2 |
Material | zinc and aluminum die-cast |
Cooling | convection |
Operating/storage temperature | 0…+50°C/-25…+85°C |
Protect. rating/installation pos. | IP65/67/variable |
Loading content ...
© Beckhoff Automation 2024 - Terms of Use