The EJ2819 EtherCAT plug-in module connects the binary 24 V DC control signals from the automation device on to the actuators at the process level with electrical isolation. The module has 16 channels, whose signal states are indicated by LEDs. The integrated diagnostics can be evaluated in the controller and is indicated by the LEDs. Maintenance of the application is simplified by the diagnostics. The reference ground for the outputs is 0 V UP. The outputs are electrically isolated from the fieldbus side.
Special features:
- connection of different load types possible (resistive, inductive, capacitive)
- max. output current 0.5 A per channel
- short-circuit-proof outputs and reverse polarity protection
- integrated diagnostics option, including
- short-circuit detection per channel
- wire breakage per channel
- overcurrent per channel
- overtemperature
- voltage loss and undervoltage
- parameterizable output behavior in case of bus error (safe state)
Product status:
regular delivery
Product information
| General | EJ2819 |
|---|---|
| Number of channels | Total | 16 |
| Internal communication protocol | EtherCAT |
| Digital output | EJ2819 |
|---|---|
| Standard digital | Positive switching | |
| Number of channels | 16 |
| Load type | resistive, inductive, capacitive |
| Signal range | Nominal | 24 V DC |
| Signal range | Technical | 20.4…28.8 V DC |
| Output current | max. 0.5 A per channel |
| Short-circuit proof | yes |
| Short-circuit current limit | typ. < 1 A |
| Output stage | push |
| Switching times | TON | typ. 80 µs |
| Switching times | TOFF | typ. 80 µs |
| Reverse polarity protection | yes |
| Switching-off energy | Inductive | < 150 mJ per channel |
| Diagnostics | yes |
| Wire break detection | yes |
| Short-circuit detection | yes |
| Overload | yes |
| XFC | EJ2819 |
|---|---|
| Distributed clocks | no |
| Timestamp | no |
| Oversampling | no |
| Supply and electrical isolation | EJ2819 |
|---|---|
| Electronics | Supply voltage | via 24 V UP |
| E-bus | Current consumption | typ. 120 mA |
| Power contacts | Current consumption | typ. 30 mA + load |
| Electrical isolation | Channel/bus | functional, 707 V DC type test |
| Environmental conditions | EJ2819 |
|---|---|
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Installation position | see documentation |
| Standards and approvals | EJ2819 |
|---|---|
| Vibration resistance | conforms to EN 60068-2-6 |
| Shock resistance | conforms to EN 60068-2-27 |
| EMC immunity | conforms to EN 61000-6-2 |
| EMC emission | conforms to EN 61000-6-4 |
| Markings | CE |
| Housing data | EJ_12_16pin_Code14 |
|---|---|
| Weight | approx. 30 g |
| Protection rating | IP20 |
| Material | polycarbonate |
| Dimensions | Width (single) | 12 mm |
| Dimensions | Height | 66 mm |
| Dimensions | Depth | 55 mm |
| Installation | 2 x 20-pin socket strip on signal distribution board |
| Connection mechanism | application-specific plug on the signal distribution board |
| Mechanical coding | yes |