| Technical data | EJ4132 |
|---|---|
| Connection technology | 2-wire, single-ended |
| Number of outputs | 2 |
| Signal voltage | -10…+10 V |
| Distributed clocks | yes |
| Distributed clock precision | << 1 µs |
| Load | > 5 kΩ (short-circuit proof) |
| Output error | < 0.1% (relative to end value) |
| Resolution | 16 bit (incl. sign) |
| Electrical isolation | 500 V (E-bus/field potential) |
| Conversion time | ~ 40 µs |
| Current consumption periphery | – |
| Current consumption E-bus | typ. 185 mA |
| Special features | Watchdog parameterizable; user synchronization can be activated. |
| Weight | approx. 30 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, UL |
| Housing data | EJ_12_16pin_Code17 |
|---|---|
| Design form | EtherCAT I/O plug-in module |
| Material | polycarbonate |
| Installation | on signal distribution board |
| Mechanical coding | EJ plug-in module: signal-specific coding pins on the housing, signal distribution board: holes in the printed circuit board |
| Position of the coding pins | 1, 7 |
| Locking | latching lug in circuit board cut-out |
| Connection method | field wiring: application-specific wiring level on the signal distribution board,
EJ plug-in module: 2 x 20-pin socket strip |
| Dimensions (W x H x D) | 12 mm x 66 mm x 55 mm |