ELX4184 | EtherCAT Terminal, 4-channel analog output, current, 4…20 mA, 16 bit, single-ended, HART, Ex iNew

Image similar, may contain optional accessories
ELX4184 | EtherCAT Terminal, 4-channel analog output, current, 4…20 mA, 16 bit, single-ended, HART, Ex i

ELX4184 | EtherCAT Terminal, 4-channel analog output, current, 4…20 mA, 16 bit, single-ended, HART, Ex i

Run
HART/Error 1, 2
HART/Error 3, 4
Power contact
+24 V Ex
Power contact
0 V Ex
Output 1, GND
Output 2, GND
Output 3, GND
Output 4, GND
ELX4184 | EtherCAT Terminal, 4-channel analog output, current, 4…20 mA, 16 bit, single-ended, HART, Ex i

ELX4184 | EtherCAT Terminal, 4-channel analog output, current, 4…20 mA, 16 bit, single-ended, HART, Ex i

The analog ELX4184 EtherCAT output terminal allows intrinsically safe HART-capable field devices from hazardous areas in zones 0/20 and 1/21 to be connected directly. The ELX4184 can be used to control intrinsically safe controllers for control valves, for example. The status and error LEDs provide information about the state of the HART communication and signal any communication errors.

 

The HART (Highway Addressable Remote Transducer) protocol enables two-way communication through digital data transfer via the analog 4…20 mA wiring. In this way, further data can be exchanged with the field device via the superimposed digital signal, in addition to the analog current signal.

 

HART communication can also be used for the FDT/DTM concept. The TwinCAT FDT Container enables field device DTMs to be directly integrated into TwinCAT Engineering. This means that field device configuration and diagnostics are already available in the development environment. As the FDT concept only supports 32 bits, it cannot be applied in the 64-bit TwinCAT XAE Shell.

Product status:

product announcement | estimated market release 2nd quarter 2026

Product information

Technical dataELX4184
Technologycurrent output
Signal current4…20 mA
Number of outputs4 (single-ended)
Connection technology2-wire
Load< 400 Ω
Resolution16 bit (incl. sign)
Conversion timetyp. 1 ms
Supply voltage electronics24 V DC (via power contacts), ELX9560 power supply
Current consumption power contactstyp. 20 mA + load
Current consumption E-bustyp. 70 mA
Distributed clocks
Special featuresparameterizable watchdog, activatable user calibration
Weightapprox. 90 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/see documentation
Approvals/markingsCE, ATEX, IECEx (in preparation)
Housing dataELX-24-2x8pin
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate, blue
Dimensions (W x H x D)24 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxxx series
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG28…14,
st*: AWG28…14,
f*: AWG26…16
Stripping length8…9 mm
Power contacts2 blade/spring contacts

*s: solid wire; st: stranded wire; f: with ferrule