The FC532x PC plug-in cards connect the PC (PCI Express®) to a CAN FD network. CAN FD is a further development of the very common CAN hardware. The advantage of CAN FD is that up to 64 bytes of data can be sent and received in one CAN frame by operating the data range with a higher baud rate. The option is also available to operate the FC532x CAN FD cards in the classic CAN mode of the FC512x CANopen card. The CAN FD functionality can be operated via the CAN interface and enables layer-2 access. If the card is operated as a CANopen master/slave, only the classic CAN mode can be used.
Product status:
regular delivery
Product information
| Technical data | FC5322 |
|---|---|
| Fieldbus | CANopen master/slave interface (classic CAN), CAN FD |
| PC interface | PCI Express® x1 |
| Number of channels | 2 |
| Data transfer rates | max. 5…8 Mbit/s in data phase, max. 1 Mbit/s in arbitration phase |
| Bus interface | 2 x D-sub plug, 9-pin |
| Termination resistor | switchable |
| Bit width in the process image | total max.: 4 kbyte input and output data |
| Hardware diagnostics | 2 LEDs per channel |
| Driver | TwinCAT 3.1 |
| Dimensions (W x H x D) | single slot, approx. 100 mm x 130 mm |
| Operating temperature | 0…55°C |
| Material compliance | FC5322 |
|---|---|
| CAS No. | 7439-92-1 |
| REACH SVHC | Lead |
| REACH Annex XVII | compliant |
| REACH Annex XIV | compliant |
| SCIP No. | d8d5ad4a-85c5-43c8-a5ce-a91d08db9ac2 |
| POP | compliant |
| RoHS | compliant with exemption |
| RoHS exemption | 6c: Copper alloy with a mass fraction of up to 4% lead, 7c-I: Lead-containing electrical and electronic components in glass and ceramic materials, excluding dielectric ceramics in capacitors |
| China-RoHS | www.beckhoff.com/china-rohs-ipc |
| CA Prop65 | www.beckhoff.com/prop65 |
| Disclaimer | This statement and the information contained above are, to the best of our knowledge and belief, accurate, based on the information we have received from our suppliers. This information is in line with the current standard of technology and our suppliers’ technical documentation. The absence of the substances is not verified by Beckhoff Automation by means of analytical tests. When addressed to our customers any information contained in this document is subject to the terms and conditions expressed in the governing customer agreement. Our general terms and conditions apply. |