EP6228-0044 | EtherCAT Box, 8-channel communication interface + 8-channel digital combi, IO-Link, master, Class A, M12, L-codedNew

Image similar, may contain optional accessories
EP6228-0044 | EtherCAT Box, 8-channel communication interface + 8-channel digital combi, IO-Link, master, Class A, M12, L-coded

EP6228-0044 | EtherCAT Box, 8-channel communication interface + 8-channel digital combi, IO-Link, master, Class A, M12, L-coded

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power IN
Power OUT
1 | Tx+
2 | Rx+
3 | Tx-
4 | Rx-
1 | L+
2 | Input
3 | L-
4 | C/Q
5 | n. c.
1 | GNDP
2 | GNDS
3 | FE
4 | +24 V DC US
5 | +24 V DC UP
EP6228-0044 | EtherCAT Box, 8-channel communication interface + 8-channel digital combi, IO-Link, master, Class A, M12, L-coded

EP6228-0044 | EtherCAT Box, 8-channel communication interface + 8-channel digital combi, IO-Link, master, Class A, M12, L-coded

The EP6224-0044 IO-Link master module enables connection of up to eight IO-Link devices. These can be IO-Link box modules, actuators, sensors or combinations of both. In addition, the EP6224-0044 offers eight further digital inputs or outputs on the eight Class A master ports.

The EtherCAT Box is parameterized via the EtherCAT master. The parameterization of the IO-Link devices can take place from TwinCAT via ADS or, very conveniently, via the integrated IO-Link configuration tool.

In the default setting, the eight C/Q channels of the EP6224-0044 work as IO-Link channels. Each IO-Link channel can also optionally be used just as an input or output channel.

The L-coded M12 power supply connectors offer an increased total current of the EtherCAT Box, so that all IO-Link ports and inputs/outputs can be operated with the maximum current.

Product status:

product announcement | estimated market release 4th quarter 2025

Product information

Technical dataDigital input/output
Nominal input voltage24 V DC (-15%/+20%)
Input filter10 µs
“0” signal voltage-3…+5 V
“1” signal voltage11…30 V (EN 61131-2, type 3)
Input currenttyp. 3 mA (EN 61131-2, type 3)
Load typeohmic, inductive, lamp load
Switching timestyp. TON: 60 µs, typ. TOFF: 300 µs
Short-circuit currenttyp. 1.9 A
Technical dataOther channels
Data transfer rates4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Specification versionIO-Link V1.1, Class A
IO-Link interfaces8
IO-Link sensor supply L+24 V DC, 1.6 A per port, ∑ 16 A for 8 ports
IO-Link extra power P24
IO-Link (C/Q)max. 500 mA in DO mode
Technical dataGeneral
ProtocolEtherCAT
Bus interface2 x M12 socket, 4-pin, D-coded
Connection methodM12 socket, 5-pin, a-coded
Number of inputs8 additional digital inputs or outputs
Rated load voltage24 V DC (-15%/+20%)
Max. output current0.5 A per channel, individually short-circuit proof, ∑ 16 A
Nominal voltage24 V DC (-15%/+20%)
Distributed clocksyes
Current consumption from UStyp. 130 mA + load
Power supply connectionfeed: 1 x M12 plug, L-coded, 4 + FE, downstream connection: 1 x M12 socket, L-coded, 4+ FE
Electrical isolation500 V
Weightapprox. 440 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL (in preparation)
Housing dataM12, L-coded
Dimensions (W x H x D)60 mm x 150 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4