The EP4304-1002 EtherCAT Box has two analog inputs, two analog outputs and two digital inputs, which can be parameterized individually, so that they either process or generate signals in the ±10 V range. The voltage signals have 16-bit resolution. The analog channels have a common ground potential with the UP/24 V DC supply. On each M12 there is a digital type 3 input with 10 µs input filter time and an analog input and an analog output. Since the digital input and analog inputs/outputs are arranged together on one M12 each, complex terminal devices can be controlled with a single connection cable. This saves additional costs, cable channels and installation work.
Special features:
- analog input and output at one port
- additional digital input for error messages, etc.
- compact, narrow IP67 design
Product status:
regular delivery
Product information
| Technical data | EP4304-1002 |
|---|---|
| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
| Number of outputs | 2 x analog |
| Number of inputs | 2 x analog, 2 x digital |
| Input/output connections | M12 x 1, 5-pin, a-coded |
| Signal type | -10/0…+10 V |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Load | output: 5 kΩ |
| Internal resistance | input: > 200 kΩ |
| Resolution | 16 bit |
| Conversion time | input: ~ 100 µs, output: ~ 40 µs |
| Measurement error/uncertainty | input: < 0.3%, output: < 0.1% (each relative to full scale value) |
| Actuator supply | from the auxiliary voltage UP |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Electrical isolation | 500 V |
| Current consumption from US | 120 mA |
| Special features | combi module, inputs and outputs |
| Weight | approx. 165 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL |
| Housing data | 8 x M8, 4 x M12 |
|---|---|
| Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
| Material | PA6 (polyamide) |
| Installation | 2 fixing holes 3.5 mm diameter for M3 |