ZB7001 | EtherCAT P cable, shielded, PUR, drag-chain suitable, (1 x 4 x AWG24/7), black with red stripe, OD = 5.2 mm (±0.2 mm)

Electrical data  
Rated voltage max. 300 V (peak value, not for high voltage purposes)
Operating voltage ≤ 125 V (peak value, not for high voltage purposes)
Attenuation of shielding min. 80 dB between 30 MHz and 125 MHz (type test)
Insulation resistance ≥ 5GΩ * km
Unbalanced capacitance to ground ≤ 2000 pF/km
Mutual capacitance nom. 50 nF/km
Characteristic impedance (Ethernet) 100 Ω ±15 Ω
Loop resistance 175.2 Ω/km
Dielectric strength wire/wire (Ethernet) 1 kV (50 Hz, 1 min.)
Dielectric strength wire/shield (Ethernet) 1 kV AC (50 Hz, 1 min.)/1 kV DC (50 Hz)
Signal running time (Ethernet) 4.8 ns/m
Electrical parameters (Ethernet) based on CAT 5
Test voltage 750 V, 50 Hz, 1 min.
Mechanical data  
Cable structure (Ethernet) star quad
Conductor construction (Ethernet) 7-strand
Cross section (Ethernet) 1 x 4 x 0.22 mm² (AWG24)
Min. bending radius, moved 15 x outer cable diameter
Min. bending radius, moved in drag chain 15 x outer cable diameter
Min. bending radius, fixed installation 8 x outer cable diameter
Weight 42 kg/km (28.2 lb/1000 ft)
Outer cable diameter 5.2 mm ± 0.2 mm (0.2047" ± 0.0079")
Conductor material (Ethernet) copper, tinned
Shielding aluminium-clad foil, braiding of tinned copper wires, coupling
Optical covering factor of shielding (Ethernet) ≥ 85 %
Use drag-chain suitable
Max. acceleration 35 m/s²
Max. speed 5 m/s
Max. travel distance 10 m
Max. number of cycles 3 million
Jacket colour black (similar to RAL 9005) with red stripe (similar to RAL 3020)
Material jacket PUR (polyurethane)
Wire colour code yellow, orange, white, blue
Wire insulation material PO (Polyolefine)
Printing on the jacket Beckhoff Automation GmbH & Co. KG - Germany - EtherCATp Cat5e AWG24/7 E170315 AWM 21198 AWM I/II A/B 80°C 300 V MM/YY RoHS
Printing colour white
Environmental data  
Operation temperature range, moved -30…+70 °C, -22…+158 °F
Operation temperature range, fixed installation -40…+80 °C, -40…+176 °F
UV resistance good
Oil resistance according to DIN EN 60811-404
Flame-retardant Horizontal flame test according to UL 1581 part 1090
Halogen-free according to IEC 60754 respectively DIN VDE 0472 part 815
Attenuation  
Max. insertion loss
Frequency [MHz] 1 4 10 16 20 31.25 62.5 100
[db/100 m] 3.0 6.0 9.5 12.1 13.5 17.1 24.8 32.0
[db/100 ft] 0.9 1.8 2.9 3.7 4.1 5.2 7.6 9.8
Min. near-end crosstalk attenuation
Frequency [MHz] 1 4 10 16 20 31.25 62.5 100
[db/100 m] 65 56.3 50.3 47.2 45.8 42.9 38.4 35.3
[db/100 ft] 19.8 17.2 15.3 14.4 14 13.1 11.7 10.8
Ordering information Length
ZB7001 sold by the metre

Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT G®, EtherCAT G10®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC®, XTS® and XPlanar® are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.

 

© Beckhoff Automation GmbH & Co. KG 05/2020

 

The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual application do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressively agreed in the terms of contract.