ZK1090-3291-3xxx | EtherCAT cable, PVC, AWG 26, fixed installation

M8, socket, straight, female, 4-pin, A‑coded – RJ45, plug, straight, male, 8-pin

Plugs

Electrical data Head A Head B
Rated voltage 30 V (according to IEC 61076-2-101) 125 V (according to IEC 61076-2-101)
Rated current 4 A at 40 °C (according to IEC 61076-2-101) 1 A at 50 °C
Shielding yes yes
Insulation resistance ≥ 100 MΩ (according to IEC 60512) ≥ 10 GΩ (according to IEC 60512-2)
Mechanical data    
Installation size M8 RJ45
Connector type socket plug
Configuration straight straight
Contact type female male
Number of positions (face) 4-pin 8-pin
Coding A‑coded -
Recommended torque, nut 0.4 Nm -
Mating cycles ≥ 100 ≥ 750
Way of locking screw -
Weight per piece 0.028 kg (0.0617 lb) -
Body colour black black
Body material TPU, UL94 PC UL 94-V-2
Coupling nut material CuZn, Ni -
Seal FPM -
Contact carrier colour green -
Contact carrier material PA 6, UL 94 V-0 -
Contact material CuZn CuZn
Contact plating Ni, Au gal. Ni, Au gal.
Environmental data    
RoHS compliant yes yes
Ambient temperature, operation -30...+85 °C, -22...+185 °F -40...+85 °C, -40...+185 °F
Protection class IP 67 in screwed condition (according to IEC 60529) IP 20
Pollution level 3/2 (according to IEC 60664-1) -

Cable

Electrical data  
Rated voltage 30 V
Attenuation of shielding ≥ 43 dB
Insulation resistance ≥ 500 MΩ/km
Unbalanced capacitance to ground 1600 pF/km
Mutual capacitance 52 nF/km
Characteristic impedance (Ethernet) 100 Ω ±5 Ω (100 MHz) (EN 50289-1-11)
Loop resistance (Ethernet) 280 Ω/km
Unbalanced resistance (Ethernet) 2 %
Signal running time (Ethernet) 5.3 ns/m
Electrical parameters (Ethernet) CAT 5e, according to EN 50288-2-2
Test voltage ≥ 2000 V
Mechanical data  
Cable structure (Ethernet) star quad
Conductor construction (Ethernet) 7 x 0.167
Cross section (Ethernet) 0.14 mm² (AWG26)
Min. bending radius, moved 7 x outer cable diameter
Min. bending radius, fixed installation 5 x outer cable diameter
Weight 33 kg/km (22.2 lb/1000ft)
Outer cable diameter 4.9 mm ± 0.2mm (0.193" ± 0.0079")
Optical covering factor of shielding (Ethernet) ≥ 80 %
Use fixed installation
Wall thickness of wire insulation (Ethernet) 0.25 mm
Jacket colour green
Material jacket PVC (polyvinyl chloride)
Wire colour code yellow, orange, white, blue
Wire insulation material PE (polyethylene)
Printing on the jacket "sequential length in metres" Industrial Ethernet Cat5 flex *E130266 AWM STYLE 2464 80 °C 300 V* ZB9030 "month/year" "internal order number"
Printing colour black
Environmental data  
Operation temperature range, fixed installation -40…+80 °C, -40…+176 °F
Flame-retardant acc. to IEC 60332-1-2
Halogen-free DIN VDE 0472 part 815
Approvals UL-Style 2464
Attenuation  
Max. insertion loss
Frequency [MHz] 1 4 10 16 20 31.25 62.5 100
[db/100 m] 3.2 6.0 9.5 12.1 13.6 17.1 24.8 32.0
[db/100 ft] 1 1.8 2.9 3.7 4.1 5.2 7.6 9.8
Min. near-end crosstalk attenuation
Frequency [MHz] 1 4 10 16 20 31.25 62.5 100
[db/100 m] 65.3 56.3 50.3 47.2 45.8 42.9 38.4 35.3
[db/100 ft] 19.9 17.2 15.3 14.4 14 13.1 11.7 10.8
Contact assembly  
Dimensions  
 
 
A1 40.00 mm
A2 14.00 mm
B1 44.00 mm

Notes

- Depending on the cable length (L), the following length tolerances apply:

  0 m…<0.2 m: ± 10 mm | 0.2…4.0 m: + 40 mm | ≥ 4.0 m: + 1 %

- Illustrations similar

- Further cable length on request. The last three digits of the ordering information is the cable length in decimeters, e.g.ZKxxxx-xxxx-x020 = cable length 2.00 m

Ordering information Length
ZK1090-3291-3005 0.50 m
ZK1090-3291-3010 1.00 m

Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.

 

© Beckhoff Automation GmbH & Co. KG 09/2018

 

The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual application do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressively agreed in the terms of contract.